Engineering
26
218150 / 948260310020
2015-12-16·BA00·III·en·01
Temperature Input Module Zone 2
Series 9482/33
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Type of circuitry I: RTD and TC Mixed with ext. CJC, grounded
16561E00
Up to 8 earthed thermocouples or mV transmitters with external reference junction
NOTE
The following safety data are only applicable to the combined wiring of earthed
•
resistance temperature detectors and resistance teletransmitters
•
thermocouples and mV transmitters with external reference junction
The safety data for the resistance sensors, the thermocouples and the external
reference junction must be determined separately. Resistance temperature detectors or
resistance teletransmitters can be connected in any constellation of 2, 3 and 4
conductors. A mixture of resistance sensors and thermocouples inside the same
channel is also possible. The external reference junction may only be connected to
channels 6 and 7.
Installation type
earthed
Reference junction
external
Max.
output voltage Uo ext
12.92 V
Max. current Io
25.0 mA
Max. power Po
81.0 mW
Max. input voltage Ui
6.5 V
Note
max. input voltage Ui is the sum of all inputs
Max. connectable
Inductance Lo /
capacity Co
IIC
IIB / IIIC
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
mV
T
T
T
T
Lo [mH]
72
50
10
2
1
0.5
0.2
Co [
m
F]
0.17
0.22
0.34
0.46
0.53
0.62
0.78
Lo [mH]
100
20
5
1
0.5
0.2
0.1
Co [
m
F]
1.2
1.6
2.1
3.0
3.5
4.5
5.7
Summary of Contents for 9482/33