iRBX6GF User’s Manual
UM-iRBX6GF-4.5.1-EN.docx
Pages 10 of 119
Table 3 – Port Naming
iRBX DIN Rail Face
Panel Port Names
Internal Port
Names
Description
Operation Mode
P1/A
PORT 1
Redundancy port A
HSR/PRP
P2/B
PORT 2
Redundancy port B
HSR/PRP
P3/A*
PORT 3
Inter-link port
Switching Port
P4/B*
PORT 4
Inter-link port
Switching Port
P5
PORT 5
(I) Inter-link port**
Switching Port
P6
PORT 6
Inter-link port
Switching Port
MGMT
MGMT
Management Port
Management Port
Note
: *
The ports P3/A and P4/B are not supporting HSR/PRP functionality.
** Port 5 is Interlink port when HSR-PRP-A/B coupling mode is used
3.4
Bottom View Panel
The Phillips Screw Terminal Block, which is located on the bottom of the unit, has Phillips screws with
compression plates that allow bare wire connections or crimped terminal lugs. To ensure secure and
reliable connections under severe shock or vibration, the use of #6 size ring lugs is recommended.
The terminal block comes with a safety cover that must be removed before connecting any wires. The
cover must be reattached after wiring for ensuring safety of personnel.
The iRBX6GF series support dual redundant power supplies (PWR1 and PWR2). There are 3 options:
•
LV: Dual Input 9-36VDC
•
MV: Dual Input 36-75VDC
•
HV: Input 110-370VDC or 90-264VAC.
There are also connections for Failsafe Relay. The Failsafe Relay is rated 1A @ 24VDC. The connections
to the terminal block are listed in the table below.
Table 4 – Power Connection