iRBX6GF User’s Manual
UM-iRBX6GF-4.5.1-EN.docx
Pages 11 of 119
Terminal
Number
Description
Connection
1
PWR1 (L)—Live
Connect to the (Live) of DC Power Supply 1 or (Live) terminal of an
AC power source.
2
PWR1 (G)—Ground DC Power Supply 1 ground connection or AC power round
connection
3
PWR1 (N)—Neutral Connect to the Neutral of the DC Power Supply 1 or (Neutral)
terminal of an AC power source.
4
G—Chassis Ground Connected to the ground bus for DC inputs or Safety Ground
terminal for AC Units. Chassis Ground connects to both power
supply surge grounds via a removable jumper.
5
PWR2 (L)—Live
Connect to the (Live) terminal of Power Supply 2 or backup DC
power source.
6
PWR2 (G)—Ground Power supply 2 or backup DC power source ground connection.
7
PWR2 (N)—Neutral Connect to the (Neutral) terminal of Power Supply 2 or backup DC
power source.
8
FAIL Open
Fault Relay
9
FAIL RLY
Fault Relay
10
FAIL Close
Fault Relay
Chassis Ground Connection
The iRBX6GF’s chassis ground connection, which is located next to the terminal block, uses a #6-32
screw. We recommend terminating the ground connection using a #6 ring lug and a torque setting of 15
in.lbs (1.7Nm).
100-240VAC rated equipment: A 250VAC appropriately rated circuit
breaker must be installed.
Equipment must be installed according to the applicable country wiring
codes.
When equipped with a HI voltage power supply and DC backup,
120-370VDC rated equipment: A 370VDC appropriately rated circuit
breaker must be installed.
A circuit breaker is not required for DC power supply voltages of 10-48VDC.
For Dual DC power supplies, separate circuit breakers must be installed and
separately identified.
Equipment must be installed according to the applicable country wiring