Group access: Ramp speed
(Read-write /Write access)
Read-write
Byte
DATA_ID
Controller (DLC = 1):
Bit
7
6
5
4
3
2
1
0
Read actual ramp speed of module
Designation
DATA
_DIR
Data
1
1
1
0
1
0
0
0
0
Description
read
⇓
Response module (DLC = 3)
Byte
DATA_ID
DATA_1
DATA_0
Bit
7
6
5
4
3
2
1
0
7
...
0
7
0
Designation
DATA
_DIR
Data
0
1
1
0
1
0
0
0
0
...
x8 x7
...
x0
Description
write
x8 ... x0:
Ramp speed of module with resolution V
O max
/ 50000s
Write
(Controller [DLC = 3]: Write ramp speed module)
Byte
DATA_ID
DATA_1
DATA_0
Bit
7
6
5
4
3
2
1
0
7
...
0
7
0
Designation
DATA
_DIR
Data
0
1
1
0
1
0
0
0
0
...
x8 x7
...
x0
Description
write
x8 ... x0:
Ramp speed of module with resolution V
O max
/ 50000s
Ramp speed range:
V
O max
/ 2500s
≤
Ramp speed
≤
V
O max
/ 10s )
1
Ramp speed higher than the maximum module specific
ramp speed will be ignored and the Bit ‘ Input error’ in the
‘Status channel’ will be set
.
)
1
: sub values are rounded down to the next lower value, according to the resolution.
Group access: Set voltage for all channels
(Write access)
Controller (DLC = 4): Set voltage for all channels
Byte
DATA_ID
DATA_2 / DATA_1
DATA_0
Bit
7
6
5
4
3
2
1
0
7
...
0
7
...
0
Designation
DATA
_DIR
LSB
Data
0
1
1
1
0
0
1
0
0
Description
write
Set voltage for all channels with resolution
V
O max
/ 10
∗
exp6 [V] in DATA_2 to DATA_0
If any channel is ‘ON’ then the voltage of which will be ramped on set voltage after the receipt of this write
access.
If any channel is ‘OFF’ then the set voltage of which will be stored in the module and after the channel will be
switched ‘ON’ ramping will be started up to the set voltage.
Set voltages higher than the maximum specific module voltage are ignored and the bit ‘Input Error’ in ‘Status
channel’ will be set.