iSMA-B-MG-IP User Manual
www.ismacontrolli.com
DMP260en | 1st Issue rev. 6 | 05/2022
page 16 of 29
Baud rate
Protocol
1
1
1
115200
Table 7. Setting baud rate and protocol
5.3.3 Counter of Received Messages (30004)
The 32-bit register with the number of valid Modbus messages received by the device
from last powering up. The value is reset after a power cycle or after changing
transmission parameters (speed, stop bits, parity, etc.).
5.3.4 Counter of Error Messages (30006)
The 32-bit register with the number of error Modbus messages received by the device
from last powering up. The value is reset after a power cycle or after changing
transmission parameters (speed, stop bits, parity, etc.).
5.3.5 Counter of Sent Messages (30008)
The 32-bit register with the number of Modbus messages sent by the device from last
powering up. The value is reset after a power cycle or after changing transmission
parameters (speed, stop bits, parity, etc.).
5.3.6 Hardware_Version (30130)
This 16-bits register contains the module hardware version multiplied by 10.
5.3.7 MAC_Address (30131)
This 32-bits register contains the module MAC address information.
5.3.8 Device Actions (40001)
Setting the 40001 register according to the table below will enable 1 of 4 available
actions: reset module, reload settings, set to default, and enter bootloader.
Value
Action
511
Reset
767
Reload settings
1023
Set to default
1279
Enter Bootloader
Table 8. Device actions
5.3.9 Baud Rate (40136)
If sections 1, 2, and 3 of the S3 DIP switch are in off position, the baud rate is determined
in accordance with this register. Baud rate is determined by the following formula: