iSMA-B-MG-IP User Manual
www.ismacontrolli.com
DMP260en | 1st Issue rev. 6 | 05/2022
page 26 of 29
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Data Bits:
read/write, the number of data bits transmitted in a single byte
(7 or 8);
Parity Bits:
read/write, transmission protection as a parity bit added before stop bit
(bits);
Received Frames:
read-only, the number of received frames;
Transmitted Frames:
read-only, the number of transmitted frames;
Error Frames:
read-only, the number of error frames.
7.5 IP Configuration
This page allows to change parameters of the Ethernet port, Modbus TCP IP, M-Bus TCP
IP, and M-Bus UDP IP.
Figure 20. IP configuration page
This page allows to set parameters such as:
IP Address:
read/write, the
controller’s
Ethernet interface IP address;
Mask:
read/write, the network mask;
Gateway:
read/write, the network default gateway;
Http Port:
read/write, the http port;
Mac Address:
read-only, the Ethernet interface MAC address;
M-Bus TCP Port:
read/write, the M-Bus TCP port number, default 6021;
M-Bus UDP Port:
read/write, the M-Bus UDP port umber, default 10002;
Protocol Type:
read-only, the DIP switch protocol selection;
Modbus TCP Port:
read/write, the Modbus TCP port number, default 502;
Modbus Address:
read-only, the Modbus device address set by rotary switches;
Modbus TCP Connection Timeout:
read/write, the timeout for TCP/IP messages;
RS485 Timeout:
read/write, the timeout for Modbus RTU/ASCII messages;
Send Modbus Errors:
read/write, enables or disables sending of Modbus error
messages.
WARNING!
To save changes, please use the Submit button
.
WARNING!
To save changes, please use the Submit button
.