iSMA-B-MG-IP User Manual
www.ismacontrolli.com
DMP260en | 1st Issue rev. 6 | 05/2022
page 29 of 29
Modbus
Address
Decimal
Address
Hex
Address
Register Name
Access
Description
40023
22
0x16
M-BUS BAUD RATE
(32 – bits)
Read/write
memory
Baud rate for M-Bus
(Default 2400 bps)
40025
24
0x18
M-BUS CONNECTION
TIMEOUT (32 – bits)
Read/write
memory
Timeout of M-Bus
connection
(Default 2000 ms)
40136
135
0x87
BAUD RATE
Read/write
memory
Transmission speed is
defined by the user
calculated using the
formula:
The value is considered
only when sections 1, 2
and 3 of S3 switch is in
the OFF position
The default value is 7680
(76800 bps)
40137
136
0x88
STOP BITS
Read/write
memory
Supported values are 1
and 2
The default value 1
40138
137
0x89
DATA BITS
Read/write
memory
Supported values are 7
and 8
The default value 8
40139
138
0x8A
PARITY BIT
Read/write
memory
Parity Bit (40139) The
default value is 0 (no
parity)
Allowed values:
Value
Descriptio
n
0 (default) none
1
Odd
2
Even
3
Always 1
4
Always 0
40140
139
0x8B
RESPONSE DELAY
Read/write
memory
Delay in ms before
sending response
The default value is 0.
Table 12. List of Modbus registers