SfAR-S-6TI User Manual
www.ismacontrolli.com
DMP272en | 3rd Issue rev. 2 | 05/2022
page 23 of 26
Modbus
Address
Decimal
Address
Hex
Address
Register Name
Access
Description
40090
89
0x59
Output 2 Settings
Read/write
+512 – Output is set if
value is less than Alarm
Value ( register 40091 or
40092) („heating")
+1024 – The lowest value
from selected inputs
+2048 – The greatest
value from selected inputs
(if not select either of the
two above options than is
used average value of
selected inputs)
40091
90
0x5A
Alarm Value 1
Read/write
Alarm value for outputs
40092
91
0x5B
Alarm Value 2
Read/write
40093
92
0x5C
Alarm Hysteresis 1
Read/write
The hysteresis value for
alarm outputs
40094
93
0x5D
Alarm Hysteresis 2
Read/write
40095
94
0x5E
Input Resistance 1
Read/write
Lead wire resistance for
each input
40096
95
0x5F
Input Resistance 2
Read/write
40097
96
0x60
Input Resistance 3
Read/write
40098
97
0x61
Input Resistance 4
Read/write
40099
98
0x62
Input Resistance 5
Read/write
40100
99
0x63
Input Resistance 6
Read/write
Table 9. Registered access
9.2 Bit Access
Modbus
Address
Decimal
Address
Hex
Address
Register Name
Access
Description
801
800
0x320
Input 1
Read
Set when the sensor is
connected
802
801
0x321
Input 2
Read
Set when the sensor is
connected
803
802
0x322
Input 3
Read
Set when the sensor is
connected
804
803
0x323
Input 4
Read
Set when the sensor is
connected