iSMA-B-LP Room Panel/Modbus
version 1.3
www.gc5.pl
Page 82 / 121
12.1.4
Fan Submenu
Modbus
Address
Dec
Address
Hex
Address
Register Name
Access
Description
40067
66
0x42
FANNUMERIC1
PRESENT_VALUE
Read &
Write
Memory
Present value of the parameter
40654
653
0x28D
FANMENUACTIVEPOINTS
Read &
Write
Memory
Number of active parameters in submenu
40657
656
0x290
FANNUMERIC1
NAME (32
–
bits)
Read &
Write
Memory
Displaying user-defined parameter name.
40659
658
0x292
FANNUMERIC1
STEP
Read &
Write
Memory
STEP during parameter value changing.
The default value is 0
40660
659
0x293
FANNUMERIC1
LOW_LIMIT
Read &
Write
Memory
Minimal value of the parameter.
The default value is 0
40661
660
0x294
FANNUMERIC1
HIGH_LIMIT
Read &
Write
Memory
Maximal value of the parameter.
The default value is 0
40662
661
0x295
FANNUMERIC1
PRIORITY
Read &
Write
Memory
Priority of the parameter for sequence of display in
Submenu
40663
662
0x296
FANNUMERIC1
CONFIGURATION
Read &
Write
Memory
Bit
Name
0
1
0 Active
Not active(def) Active(def)
2
FirstPointActive Not
decimal(def)
Decimal(def)
3
SecondPointActive Not
decimal(def)
Decimal(def)
4
ThirdPointActive Not
decimal(def)
Decimal(def)
6
C unit active
not_visible(def) visible
7
F unit active
not_visible(def) visible
8
Pa unit active
not_visible(def) visible
9
Lx unit active
not_visible(def) visible
10 ppm unit active
not_visible(def) visible
11 m3/h unit active not_visible(def) visible
12 %Rh unit active
not_visible(def) visible
13 l/s unit active
not_visible(def) visible
14 % unit active
not_visible(def) visible
15 h unit active
not_visible(def) visible
40068
67
0x43
FANNUMERIC2
Read &
Present value of the parameter