A  typical  example  of  temperature  control  would  be  heating  activation  in  remote  area  if  the 
temperature drops below 10C (50F). The following settings must be used: THERMOSTAT=HEATING, 

TEMPOFF=10 (or TEMPOFF=50 in Fahrenheit for "US" models), THERMOSTATON. With these settings 

the thermostat will keep the temperature in the range of about 10C (50F). This means that as soon 

as the room is heated up to 10C (50F) the main socket is turned off. If the current temperature in 

the room is over 10C (50F) the main socket does not turn on until the temperature drops below 10C 

(50F). 
 

Another  example  is  air  conditioning  activation  when  the  temperature  exceeds  22C 

(THERMOSTAT=COOLING, TEMPOFF=22, THERMOSTATON). This means that as soon as the room is 

cooled to 22C the main socket is turned off. If current temperature in the room is less than 22C the 

main socket does not turn on until the temperature rises above 22C. TEMPOFF could be installed in 

Fahrenheit for "US" models in that case as well. 

7.3 Temperature Monitoring – Notifications, iSocket

®

 Temperature Notifier 

You  can  receive  a  message  when  the  “switch-off”  temperature  (set  by TEMPOFF=X) is 
reached. This feature is related with thermostat and works only if thermostat is enabled. 
Before setting up such alerts you must set up at least one phone number for alerts. If 

you remove all phone numbers, then alerts will be also disabled (THERMALERT=OFF will 
be active value). 
 

Command 

Description 

Response 

Type 

ALER35
8912345678 

Set the number for SMS. This number is used in 
some other cases - Chapters 9.2, 11 and 12. You 
can install up to 10 numbers. Instructions how 

to add a number are similar to those given in 
Chapter 5.1. You must set up this number before 
doing other configurations! 

ALER3589123
45678 – OK 

30min 

ALERTNUMBER-
3589123456789 

Remove number from list 

ALERTNUMBER -
3589123456789 – OK 

30min 

ALERTNUMBER-ALL 

Remove all numbers 

ALERTNUMBER-ALL – OK  30min 

ALERTNUMBER? 

Information about numbers 

ALERTNUMBERs: 
3589123456789, 
3589223456789 

No ALERTNUMBERs! 

Inf 

THERMALERT=ON 

Enable SMS sending when TEMPOFF is reached 
and main socket is therefore deactivated. 

Works only if thermostat is enabled.

 

THERMALERT=ON – OK 

30min 

THERMALERT=OFF 

Disable SMS alert 

THERMALERT=OFF – OK  30min 

THERMALERT? 

Show current settings for THERMALERT 

THERMALERT=(OFF),ON  Inf 

TRISEALERT=35 

Set the temperature at which you should receive 
a temperature rise alert (the value from -10 to 
50 Celsius, or from 14F to 122F for "US" 

models). 

TRISEALERT=35 – OK 

30min 

TRISEALERT=OFF 

Disable temperature rise alert 

TRISEALERT=OFF – OK 

30min 

TRISEALERT? 

Show current settings for TRISEALERT 

TRISEALERT=30 

Inf 

TFALLALERT=15 

Set the temperature at which you should receive 

a temperature fall alert (the value from -10 to 
50 Celsius, or from 14F to 122F for "US" 

models). 

TFALLALERT=15 – OK 

30min 

TFALLALERT=OFF 

Disable temperature fall alert 

TFALLALERT=OFF – OK 

30min 

TFALLALERT? 

Show current settings for TFALLALERT 

TFALLALERT=5 

Inf 

 

iSocket

®

 Temperature Notifier 

iSocket

®

 Temperature Notifier - this is a feature of the iSocket device which notifies you 

in  the  event  of  the  room  temperature falling  below  or  rising  above  critical levels.  This 
feature does not affect the thermostat and can work independently.  

Summary of Contents for GSM 706

Page 1: ......

Page 2: ...play commands associated with optional features The documentation and product are subject to change without notice The software supplied with this product is the exclusive property of Intellectronics...

Page 3: ...nd Commands From Unauthorised Users 14 7 Measurement and Control of Temperature 15 7 1 Thermometer 15 7 2 Thermostat 15 7 3 Temperature Monitoring Notifications iSocket Temperature Notifier 16 7 4 Tem...

Page 4: ...ecial connector Notification will be sent when it is triggered For example it could be a motion sensor an opening doors sensor fire detector gas leakage detector and many more A built in microphone al...

Page 5: ...et manual Chapter 4 3 or reset device Chapter 15 Built in microphone Chapter 10 not available in Light model Plug to connect iSocket GSM 706 707 to the wall socket to provide power for device and for...

Page 6: ...e shows model ISGSM706UK ISGSM707UK Socket Plug NEMA 5 15 Model Numbers ISGSM706US ISGSML706US ISGSM707US ISGSML707US The figure shows model ISGSM706US ISGSM707US Socket Plug CEE 7 5 French Model Numb...

Page 7: ...ical network meets safety standards The product is designed for indoor use in dry area Do not use it in wet or chemically aggressive environments For example do not use it in the bathroom It is also n...

Page 8: ...n a car that is parked in sunshine If the battery suffers overloading and or overheating the integrated protective cut off will switch off the charging discharging for safety reasons If this happens y...

Page 9: ...n was turned off If the SIM card is not inserted correctly or is damaged the indicator POWER and OUT will signal this by specific blinks see Chapter 16 All indicators blink three times simultaneously...

Page 10: ...ut only inform you of the value These commands are available at any time You can set up the facility to reset the configuration interval see section 5 3 Control and management commands marked Ctrl in...

Page 11: ...lay OFF Signal Good 67dBm TEMP 25C ALARMF Disabled ALARM status No activity Time y m d h m s Ctrl TEMPERATURE Informs about temperature in the room See details in Chapter 7 TEMPERATURE 25C Ctrl RUNTIM...

Page 12: ...device which is not advisable The device uses two methods of protection against unauthorised access Only allowing access to authorised phone numbers Authentication by password Both methods can be used...

Page 13: ...Chapter 6 3 lists more reasons for this alternative 5 2 Password Protection The following table shows how to set a password for managing access The password must consist of 5 characters Do not use a...

Page 14: ...successfully For this purpose we have implemented notifications of each executed command If you wish to receive execution confirmations the setting hide my number should not be activated on the phone...

Page 15: ...ecurity list was configured see Chapter 5 1 and someone tries to execute a command no response will be received until you install SMSCONFIRMUNAUTH ON If you set ON value for this parameter then unauth...

Page 16: ...utes after the power is switched on The temperature reading interval is 1 minute for models manufactured after July 2012 If the thermostat is enabled the first reading will occur 10 minutes after the...

Page 17: ...NUMBER 35 8912345678 Set the number for SMS This number is used in some other cases Chapters 9 2 11 and 12 You can install up to 10 numbers Instructions how to add a number are similar to those given...

Page 18: ...r each monitored environment The value can be decided empirically by comparing with the exact thermostat temperatures measured Command Description Response Type TEMPCAL 7 Change calibration constant f...

Page 19: ...rm function will send alerts and sound the siren if connected because the sensors have been activated In this event the alarm function can be deactivated manually by using the hidden button Push the h...

Page 20: ...device will not detect new sensor triggering The device will be ready to detect sensor activity no later than one minute after completion of the notification cycle If the sensor is still active at thi...

Page 21: ...designed for switching of external electrical contacts It can switch 24VDC 2A max Connectors and sensors are not supplied with the device These can be bought directly from us or our dealer network 10...

Page 22: ...at 18 00 SCHEDULER 17 00 6 INF Send status of iSocket every Saturday at 17 00 Status information is sent to the number specified by command ALERTNUMBER see Chapter 7 3 12 Status After Resumption of P...

Page 23: ...ALDOUMS NO Remove UMS code for balance from memory SALDOUMS NO OK 30min SALDOUMS Information about SALDOUMS settings SALDOUMS 100 Inf 14 Version Information Command Description Response Type HARDWARE...

Page 24: ...to GSM network MICROPHONE yellow No light Microphone is not active Lights constantly Microphone is active now Blinks every second Device is calling to somewhere for ex call alert OUT red No light Main...

Page 25: ...th Li ion battery Store conditions 30C 50C 22F 122F for the 706 models 0C 40C 32F 104F for the 707 models with Li ion battery Important notice The 706 models can operate at low temperatures in a dry p...

Page 26: ...at it was written correctly according to the manual Read about other potential problems below The OUT indicator reports an error blinking 4 times per second If the OUT indicator blinks 4 times per sec...

Page 27: ...y loss Intellectronics does not guarantee that this product will provide uninterrupted operation of the controlled equipment this device is not an uninterruptible power supply UPS This product is not...

Page 28: ...hout the express written consent of Intellectronics and any applicable third party You may not create derivative works or use any information available in this User Manual for commercial or public pur...

Reviews: