background image

 

Generator  Contactor  Relay  Output: 

Generator contactor output is used  for energizing the 

generator contactor to transfer load to the generator. It outputs R phase of the generator from 
its normally open terminal. 
 

Alarm Relay Output: 

Alarm output is used for indicating any failure event. It outputs battery 

+ supply voltage. 
 

Fuel/Stop  Solenoid  Relay  Output

:  Used  for  energizing  the  fuel/stop  solenoid  relay  of  the 

generator. It outputs b supply voltage. It can be configured as fuel or stop solenoid by 
adjusting P23 number of parameter. 
 

Starter  Relay  Output:

  Used  for  energizing  the  starter  motor  relay.  It  outputs  battery  + 

supply voltage. 
 

Auxiliary  Relay  Output: 

Auxiliary  output  can  be  configured  as  preheat,  auto  ready  and 

motor running output. It outputs b supply voltage. 
 
 

FAILURES 

 

In  the  event  of  a  failure,  relevant  fault  LEDs  identify  the  problem  and  activate  the  alarm 
output  to  sound  the  external  horn.  If  the  failure  is  a  shutdown  failure,  the  module  will  de-
energize  the  fuel  solenoid  and  stop  the  generator.  If  it  is  a  warning  failure,  the  unit  will 
indicate the fault but continue to operate. By pressing the off button the failure can be reset. 
The alarm condition must be reset to enable the module operating again.

 

 
 
 
 

 

Overspeed/Underspeed  Failure  (shutdown):

  If  the  frequency  of  the  generator 

output  exceeds  or  falls  below  the  pre-configured  alarm  level  a  shutdown  is 
initiated. The relevant failure LED will illuminate and alarm output is energized.

 

 

High/Low  Voltage  Failure  (shutdown):

  If  the  voltage  of  the  generator  output 

exceeds or falls below the pre-configured alarm level a shutdown is initiated. The 
relevant failure LED will illuminate and alarm output is energized

 

 

High Engine Temperature Switch (shutdown):

 If the module detects a negative 

signal  from  the  high  engine  temperature  switch  (close  circuit)  while operating,  a 
shutdown is initiated The relevant failure LED will illuminate and alarm output is 
energized. 

 

Over  Current  Switch  (shutdown): 

If the  module detects a negative signal  from 

the over current switch (close circuit) while operating, a shutdown is initiated the 
relevant failure LED will illuminate and alarm output is energized.

 

 

Start/Stop  Failure  (shutdown):

  If  the  engine  does  not  fire  after  the  pre-set 

number of attempts  has  been  made a start failure shutdown will  be  initiated. The 
start/stop failure LED will  illuminate. And  if the  start signal of the generator has 
still existed while fuel solenoid de-energized, the module will indicate stop failure. 
The  start/stop  failure  LED  will  illuminate  with  the  active  signal’s  failure  LED 
which must be inactive.

 

 

Low Oil Pressure Switch (shutdown

): If the module detects a loss of signal from 

the oil pressure sender (open circuit) a shutdown is initiated. This parameter can be 
disabled by configuring P34 number of parameter. Switch position (NC, NO) can 
also  be  adjusted  by  configuring  P35  number  of  parameter.  The  relevant  failure 

Summary of Contents for AMF2.0

Page 1: ... be chosen via the push buttons mounted on the front panel While the module is in Stop mode if the menu button is pressed the 41 parameter settings which are used for controlling the generator can be adjusted So the module can be adapted to all the generator without the need of any other unit or module Features Micro processor based design Automatic engine starting and stopping Automatic load tran...

Page 2: ...ly adjustable measurement calibrations Digital display Low cost small dimensions Failures Start stop failure Low oil pressure failure High engine temperature failure Overspeed underspeed failure Auxiliary failure Over under voltage failure Over current failure Charge fail warning Inputs Outputs 3 phase mains voltage inputs Single phase generator voltage input 12 24 V battery voltage inputs Low oil...

Page 3: ... the failures and alarm output The second pressing will place the unit into the off mode And during cooling time by pressing the off button will cease the cooling operation Menu Button By pressing the menu button in auto or test mode the voltage and frequency values can be displayed on the unit If the unit is into off mode pressing the menu button will place the unit into the menu mode In menu mod...

Page 4: ...4 N Mains Neutral sensing input 5 MAINS Outputs mains R phase voltage to energies the main contactor 6 GEN Outputs alternator R phase voltage to energies the generator contactor 7 U Alternator R phase voltage sensing input 8 N Alternator Neutral sensing input 9 ALARM Positive output relay activated by any alarm condition 10 FUEL Positive output relay used to control the fuel solenoid 11 START Posi...

Page 5: ...the engine isn t fired on the first attempt and the crank timer expires the module will rest the starter for the duration of crank rest timer Once this has expired the module will once again attempt to start This will be repeated until either the engine fires or the pre set number of attempts has been completed If the engine couldn t fired the module will indicate fail to start stop alarm If the e...

Page 6: ...ttempt next cranking And after waiting the relevant timer the module will indicate start stop failure If any of voltage frequency charge and oil pressure signals rise during cranking the module will disengage the starter motor and accept the engine is fired 3 Fault Protection Delay This timer allows Oil Pressure High Engine Temperature under speed under volts Charge Fail and any delayed Auxiliary ...

Page 7: ...tdown failure by adjusting P26 Oil Pressure Input Oil pressure switch output of the generator is connected to the oil pressure input of the modul It is a negative closing switch for low oil pressure And whenever oil pressure rises during cranking the engine is accepted fired If there is no oil pressure switch in the generator P34 number of the parameter has to be selected No It can also be selecte...

Page 8: ...ed alarm level a shutdown is initiated The relevant failure LED will illuminate and alarm output is energized High Low Voltage Failure shutdown If the voltage of the generator output exceeds or falls below the pre configured alarm level a shutdown is initiated The relevant failure LED will illuminate and alarm output is energized High Engine Temperature Switch shutdown If the module detects a nega...

Page 9: ...AMING AND CONFIGURABLE PARAMETRES Modules are easily programmed and the parameters are displayed and configured by using push buttons on the front panel Once the module is in the off mode by pressing menu button the module is placed to the menu mode In menu mode the parameter number can be increased with test button and decreased with auto mode After selecting the parameter number which will be co...

Page 10: ...re type Shutdown Failure Warning Failure P27 Mains control in close mode Y yes N no P28 Default parameters N no Y yes P29 Calibrations L1 0 9 1 2 5V 9 1 2 5V P30 Calibrations L2 0 9 1 2 5V 9 1 2 5V P31 Calibrations L3 0 9 1 2 5V 9 1 2 5V P32 Calibrations GEN 0 9 1 2 5V 9 1 2 5V P33 Sleep mode enable selection Y yes N no P34 Oil pressure enable selection Y yes N no P35 Oil pressure switch position ...

Page 11: ...ter the starter motor is detected starting the generator contactor delay timer is activated After this timer expires the module will energize the generator contactor if there is no failure with the generator signals This parameter must be adjusted bigger than P11 parameter P09 Mains Contactor Delay If the mains voltage has no failure after the mains transition delay timer expires the module will i...

Page 12: ...energized and outputs battery positive voltage to indicate engine running c Auto automatic mode Auxiliary output relay is energized and outputs battery positive voltage to indicate automatic mode P22 Configurable Input Auxiliary input function can be configured as one of the following a NC Normally closed Auxiliary input is configured as shutdown failure by disconnecting the input from the battery...

Page 13: ...V each numbers subtract 2 5V from the calculated voltage P31 Calibration L3 Mains line T voltage calibration The calibration value is between 9 9 Each numbers add 2 5V each numbers subtract 2 5V from the calculated voltage P32 Calibration GEN Generator line R voltage calibration The calibration value is between 9 9 Each numbers add 2 5V each numbers subtract 2 5V from the calculated voltage P33 Sl...

Page 14: ...nnect signals ENGINE SIGNALS Engine Running The module accepts the engine running whenever these signals occur Alternator Voltage 125V Alternator Frequency P20 parameter Oil Pressure Signal configurable by P40 Charge Signal configurable by P39 Engine Stopping The module accepts the engine stopping when all the following signals don t occur Alternator Voltage 125V Alternator Frequency P20 parameter...

Page 15: ...15 Panel Cut Out 67x67mm Mounting Installation Front panel mounted with rear metal screw fixings Max allowable mounting panel thickness 3mm DIMENSIONS AND MOUNTING Dimensions in mm ...

Page 16: ...AY G R S T N R S T N R S T N G EN ER AT O R M AIN S 7 5 2 1 6 8 4 3 Ş J 14 15 16 17 OIL PRESSURE T EM PERAT URE AUX INPUT OVE R CURRENT LO A D NE G AT IV E T E RM INAL O F BAT T ER Y SH O UL D BE G R O U NDE D 12 24V C HARG E 18 19 11 10 9 12 13 M START FUEL ALARM AUX O UT PUT EM ERG ENC Y ST OP W L ...