8
Generator Contactor Relay Output:
Generator contactor output is used for energizing the
generator contactor to transfer load to the generator. It outputs R phase of the generator from
its normally open terminal.
Alarm Relay Output:
Alarm output is used for indicating any failure event. It outputs battery
+ supply voltage.
Fuel/Stop Solenoid Relay Output
: Used for energizing the fuel/stop solenoid relay of the
generator. It outputs b supply voltage. It can be configured as fuel or stop solenoid by
adjusting P23 number of parameter.
Starter Relay Output:
Used for energizing the starter motor relay. It outputs battery +
supply voltage.
Auxiliary Relay Output:
Auxiliary output can be configured as preheat, auto ready and
motor running output. It outputs b supply voltage.
FAILURES
In the event of a failure, relevant fault LEDs identify the problem and activate the alarm
output to sound the external horn. If the failure is a shutdown failure, the module will de-
energize the fuel solenoid and stop the generator. If it is a warning failure, the unit will
indicate the fault but continue to operate. By pressing the off button the failure can be reset.
The alarm condition must be reset to enable the module operating again.
Overspeed/Underspeed Failure (shutdown):
If the frequency of the generator
output exceeds or falls below the pre-configured alarm level a shutdown is
initiated. The relevant failure LED will illuminate and alarm output is energized.
High/Low Voltage Failure (shutdown):
If the voltage of the generator output
exceeds or falls below the pre-configured alarm level a shutdown is initiated. The
relevant failure LED will illuminate and alarm output is energized
High Engine Temperature Switch (shutdown):
If the module detects a negative
signal from the high engine temperature switch (close circuit) while operating, a
shutdown is initiated The relevant failure LED will illuminate and alarm output is
energized.
Over Current Switch (shutdown):
If the module detects a negative signal from
the over current switch (close circuit) while operating, a shutdown is initiated the
relevant failure LED will illuminate and alarm output is energized.
Start/Stop Failure (shutdown):
If the engine does not fire after the pre-set
number of attempts has been made a start failure shutdown will be initiated. The
start/stop failure LED will illuminate. And if the start signal of the generator has
still existed while fuel solenoid de-energized, the module will indicate stop failure.
The start/stop failure LED will illuminate with the active signal’s failure LED
which must be inactive.
Low Oil Pressure Switch (shutdown
): If the module detects a loss of signal from
the oil pressure sender (open circuit) a shutdown is initiated. This parameter can be
disabled by configuring P34 number of parameter. Switch position (NC, NO) can
also be adjusted by configuring P35 number of parameter. The relevant failure