IMB222
Rev.4.05 May 2022
33
Address 40007: Relative humidity min. peak [R]
Relative humidity minimum detected peak, expressed in tenths of percentage. This value is
stored into device non-volatile memory. Therefore, this value is permanently stored.
To reset this value, a specific action should be taken (acting on address 40102).
Address 40008: Relative humidity max. peak[R]
Relative humidity maximum detected peak, expressed in tenths of percentage. This value is
stored into device non-volatile memory. Therefore, this value is permanently stored.
To reset this value, a specific action should be taken (acting on address 40102).
Address 40009: Temperature offset[R/W]
Default value:0.0°C; Range: ±12.5°C
This value, expressed in tenths of Celsius degree, adds a positive/negative offset to the
sensor measured temperature.
For example, a +100 value of the offset adds +10.0°C to the measured temperature. If the
value of 255 is the measured temperature, the value read in register 0 will be 355
corresponding to 35.5°C.
Address 40010: Relative humidity offset[R/W]
Default value:0.0%; Range: ±12.5%
This value, expressed in tenths of percentage, adds a positive/negative offset to the sensor
measured relative humidity.
For example, a -100 value of the offset subtracts -10.0% to the measured relative humidity.
If the value of 505 is the measured relative humidity, the read value in register 1 will be 405
corresponding to 40.5%RH.
10.6.3 Process data for surface temperature sensor
•
Process data FW rel. x.xx.2 (temperature sensor)
Modbus
address
Register name
Range
Notes
E
2
P
40001
System errors
(Copy of register 40070)
--
Read only
40002
Temperature
(-40.0÷125.0) °C
Read only
40003
Min. temperature peak
(-52.5÷137.5) °C
**
Read only
X
40004
Max. temperature peak
(-52.5÷137.5) °C
**
Read only
X
40005
Temperature offset
(-12.5÷12.5) °C
Read/Write
*
X
*
The effect of parameter’s modification is immediate
.
** Values that are outside measurement range are only due to the offset setup.
10.6.4 Process data for surface temperature sensor description
Address 40001: System errors[R]
This register is a copy of 40070
Address 40002: Temperature[R]
Detected temperature values, expressed in tenths of Celsius degree. For example, a value
of 100 corresponds to a temperature of 10.0°C. The measurement range is (-40÷125)°C.