Main boiler parameters (PC)
The parameters listed in the following table are limited to those described in this handbook. The com-
plete parameter list is available in the documentation for the technician.
Param-
eter
Adjustment
range
(factory setting)
Description
01
0-1 (*)
Type of GAS supply:
**(except model 18 K)
Value 0
= for
Natural Gas (G20)
supply
Value 1
= for
Commercial Propane (G31)**
supply
Note (*): The factory setting depends on the gas type arranged in factory for the boiler.
To change the type of gas supply, it is necessary to follow the complete instructions
described in the paragraph "Gas conversion" on page 42.
03
—
It indicates the CH boiler power during the soft ignition phase.
We rec-
ommend to leave the factory setting unchanged.
04
0…99
(99)
It indicates the CH boiler power according to the maximum nominal
boiler power (maximum boiler power is determined by the gas valve
regulation).
See details in "Max heating power adjustment" on page 40.
12
0-1
(0)
Burner ignition, not modulated, to allow the combustion check. For
deeper details see paragraph "Combustion test and adjustment" on
page 39.
Value 0
= burner at
minimum
power
Value 1
= burner at
maximum
power
Note: During this function mode, there are no burner temporization
time before restarting once the primary system get the limit tem
-
perature. It means that at each burner power off, the burner will
rapidly fire up again.
13
—
Minimum fan speed (in rpm x 100).
Don't change the factory setting.
The range and the value depend on the boiler model and on the param-
eter 01 (Natural Gas G20 or Propane G31 supply setting).
14
—
Maximum fan speed (in rpm x 100).
Don't change the factory setting.
The range and the value depend on the boiler model and on the param-
eter 01 (Natural Gas G20 or Propane G31 supply setting).