Green Heating Technology
34
Param-
eter
Adj. range
(fact. set.)
and values
Description
22
0; 5…120
(0)
Enabling of Safety Thermostat on floor plant (on AUX input - see also param
-
eter 46) and delay of its operating
Remark: avoid selecting values outside of the range described and correct if necessary.
0
Disabled
- the component is not connected to AUX input
5…120
Minutes of delay
between the thermostat activation (open contact) and
boiler block.
If the thermostat deactivates, the time count resets.
46
0…2
(0)
AUX input configuration - the AUX input (see "Electrical diagram" on page
50) can be set according to its use, to affect the boiler behaviour.
0
Safety thermostat of Floor plant
- When thermostat opens (open circuit),
boiler blocks and shows a specific alarm. Both this parameter and no. 22 are
factory set to 0 so, practically, AUX input is ignored.
1
DHW Storage tank thermostat
- Don’t use because this function is not
allowed on this boiler�
Information purpose only:
in models with DHW storage, with closed
circuit it forces the storage preparation (heating).
2
Room Thermostat 3
- with closed circuit, this contact activates heating
demand at the same temperature of TA1 or Remote control.
49
0…20
(0)
Chooses the type of combustion calibration.
Remark: avoid selecting values outside of the range described and correct if necessary.
0
Manual
(CO
2
adjustment)
5
Automatic
(combustion system preset)