Green Heating Technology
36
8.
if one or more CO
2
values was outside allowed ranges, carry out the MANUal combustion calibra
-
tion (see "Combustion calibration" on page 37);
• if the manual calibration doesn't allow to adjust the CO
2
to normal values, carry out an AUTO
-
matic calibration (remove the analyser during this operation) and then do a manual calibration
again, measuring and adjusting the CO
2
. If the problem persists, a fault in some component of the
combustion system should be assumed.
9.
quit the technical menu and set the boiler to
mode;
IMPORTANT: at the end of the check or the adjustments, it is INDISPENSABLE:
• close the flue plugs used, by restoring the tapping insert
2
and the screw
1
, caring that the plastic
surface of the flange is not damaged or worn;
• check the correct flue system tightness, especially the tightness of the tapping insert
2
�
Power adjustment tables
HEAT INPUT
Value of
par. 4
kW
kcal/h
City Class 25 K
MIN. 2.50
2150
00
4.61
3965
10
6.75
5805
20
9.25
7955
30
11,87
10208
40
14,14
12160
50
16,50
14190
60
18,75
16125
70
20.00
17200
78*
20,75
17845
80
23,20
19952
90
MAX. 25.00
21500
99
HEAT INPUT
Value of
par. 4
kW
kcal/h
City Class 30 K
MIN. 3.00
2580
00
7.00
6020
10
9.89
8505
20
12.53
10776
30
14.99
12891
40
17.03
14646
50
19.83
17054
60
21.96
18886
70
24.00
21044
78*
24.47
23039
80
26.79
25800
90
MAX. 30.00
25078
99
HEAT INPUT
Value of
par. 4
kW
kcal/h
City Class 35 K
MIN. 3.5
3010
00
5.9
5117
10
9.1
7800
20
11.8
10148
30
14.7
12625
40
17.5
15016
50
20.4
17578
60
23.3
20029
70
26.2
22558
80
28.0
24080
83*
29.1
24992
90
MAX. 33.2
28552
99
*
Factory setting