Technical data
TECHNICAL DATA
U.M.
City Class 20 FR
City Class 25 FR
Gas type
G20
G30/G31
G20
G30/G31
Class
II
2H3+
II
2H3+
Type
B22 - C12 - C32 - C42 - C52 - C62 - C82
Working temperature range
(min÷max)
°C
0 ÷ +60
0 ÷ +60
Max heat input (Qn)
kW
21.0
20.5
25.7
25.5
Min heat input (Qr)
kW
9.5
10.0
10.0
10.2
Max heat output (Pn)
kW
19.5
19.0
24.0
23.8
Min heat output (Pr)
kW
8.1
8.5
8.5
8.6
NO
X
Class
3
3 / 3
3
3 / 3
CO at 0% O
2
(at Qn)
ppm
69.7
87.5 / 60.9
91.1
119.7 / 79.4
CO
2
at nominal input
%
5.5
6.4 / 6.3
7.2
8.1 / 7.9
Flue temperature (at Qn)
°C
118
110 / 112
119
111 / 113
Flue mass flow rate (at Qn)
kg/h
53.74
53.62 / 54.22
51.93
53.21 / 53.82
Efficiency
Nominal efficiency (at Qn)
%
92.7
93.3
Efficiency at 30% Qn
%
90.5
91.0
Heating
Temperature selection range
(min÷max)
°C
35÷80
Expansion vessel
l
8
8
Expansion vessel
pre-loading pressure
bar
1
1
Loss of water pressure switch
off / on pressure
bar
0.4 / 0.9
(±0.2)
0.4 / 0.9
(±0.2)
Max working pressure
bar
3
3
Max system temperature
°C
85
85
Anti-freezing function
temperature on / off
°C
5 / 30
5 / 30
(follows)