actual
Probable cause
Suggested solutions
E22
Non-consistent stored data
user:
Cut boiler electric power supply off through the relevant external omnipolar switch and restore it after some minutes. If
shut-down continues or occurs again, call the Assistance Service.
Adjust boiler again ("Heating max. power adjustment" on page 32 and "Settings on electronic board" on page 33) to update
board memory data.
Replace management board (following operations: "Heating max. power adjustment" on page 32 and "Settings on electronic
board" on page 33).
E24
Underfloor heating system
safety thermostat triggering:
delivery temperature to
system is too high;
defect, fault or malfunctioning
of underfloor heating system.
Underfloor heating system and floor tiles are subject to sudden changes in temperature and therefore a well-built underfloor
heating system foresees one or more safety thermostats which, when intervening, shut down boiler.
Try boiler restore process by pressing
(after waiting for a sufficient period of time to enable system cooling and thermostat
deactivation). If shut-down occurs again, call the Assistance Service.
Note:
In presence of this alarm, also hot water production is blocked.
In case of no underfloor heating system
, verify integrity of the jumper connecting terminals 57 and 58 of the M12 connector
(see "Boiler electric diagram:" on page 16).
When underfloor heating system is present
, verify system delivery temperatures on boiler and control unit for low-temperature
systems (if present). Replace faulty or out-of-tolerance thermostats. Verify correct position of thermostats on system.
E31
Communication error
between Remote Control (if
present) and boiler
user:
select
Summer
mode by pressing
.
Problems on optional Remote Control electric line (passes close to power supply cables or other electromagnetic field sources,
faulty connection; cable longer than 50 metres).
E33
E34
Wiring setting error.
user:
Try boiler restoration pressing key
. If shut-down continues or occurs again, call the Assistance Service.
Refer to the electric diagram (page 16) and check connection integrity, in particular the possible connections (jumper) present
between two contacts of the same connector (on wiring connections to electronic board).
E35
Parasitic flame
Control electronics has
detected the presence of
the flame in the burner in
a moment in which it is not
foreseen
Wait for boiler automatic restoration (5 minutes) or manually restore boiler function by pressing
. If shut-down continues
or occurs again, call the Assistance Service.
Recognise any possible malfunctioning of gas valve (which does not interrupt gas flow and therefore burner stays on) or
electronics, flame control section (which detects flame presence also when this is not present).
E38
External temperature probe
(optional) failure.
External temperature probe,
which was recognised and
working, is now faulty
user:
Call Assistance Service.
Boiler works both in heating and in domestic water function, as if probe had never been installed, therefore, heating system temperature adjustment will be carried out directly and not according
to external temperature. The error is displayed to inform that the installed accessory is not efficient any more (consider that, at a superficial analysis, it looks like boiler is working properly).
Important: if boiler is electrically turned off and then on again, it is possible** that alarm is not displayed anymore, even if fault persists.
External temperature probe wiring check.
External temperature probe replacement.
**Alarm is triggered again only in case of probe resistance out of tolerance or in short circuit. Instead, in case of electric interruption of probe or relevant wiring, at power supply restoration,
boiler considers external probe as absent and, in Winter mode, works in standard mode (sliding temperature deactivated).
E39
Freezing suspected
After a black-out, when power
supply is restored, boiler
detects temperatures of
Heating and Domestic water
probes equal or lower than 0°C
Display shows alarm code E39, while boiler inhibits burner ignition and activates circulation pump, letting water flow in hydraulic
circuits.
If, in the meantime, temperatures detected by probes become higher than +1°C, alarm disappears and boiler goes back to standard
operation.
Otherwise, alarm becomes permanent and freezing of water in one or more points of the hydraulic circuit of the boiler and/or of
the system (with possible damages to frozen parts) is suspected. In this case, refer to a qualified technician.
Recognise/replace parts damaged by freeze.
E42
System error
Fault of systems inside boiler
Mains electric power supply
of out-of-tolerance
Investigate failure or fault referring to the technical documentation reserved to assistance centres.
E43
Water overtemperature on
system return
Water which goes back to boiler from heating system is too hot: besides indicating heating system malfunctioning, this might cause
emission of too hot fumes and damage exhaust system. Before this happens, a specific safety control has triggered.
Wait 20-30 minutes to let boiler and system cool, the restore boiler function by pressing
. It is not possible to restore operation
before system cooling. If boiler shuts down again, refer to a qualified technician.