28
Operation
TIME Q=0, Time interval (seconds) between two pulses to consider zero flow.
5.2.3.4 Lock code
Blocks access to the equipment configuration, allowing the pump to start and stop. When the access
code is 0000 (default value), the lock is disabled.
FLOWMETER
FREQUENCY : LOW
TIME Q=0 :
005
s
K =
l
010.77
/ puls
FLOWMETER
FREQUENCY : HIGH
K =
l
010.77
puls /
x2
x3
ENT
ENT
CONFIGURATION
SET UP
IN / OUT
PUMP CALIBRATION
DOSING MODE
SET UP
DOSING PUMP
UNITS
FLOWMETER
LOCK CODE
MODBUS
ENT
LOCK CODE
CODE
0000
%
l / h
0 0 0
0 0 0
MODE
25.0
%
l / h
0 0 0
0 0 0
MODE
25.0
5.2.3.3 Flowmeter
For a correct water flow reading, the flowmeter constant (volume/pulse or pulses/volume) must be
entered. Previously select the type of flowmeter for low or high frequency.
Low frequency:
for water meters with low frequency outputs (0.005 Hz to 30 Hz). The constant is
expressed in volume/pulse (litres/pulse; gallons/pulse).
High frequency:
for flowmeters with high frequency outputs (1 to 300 Hz). The K-factor constant is
expressed in pulses/volume (pulses/litre; pulses/gallon).
x2
ENT
ENT
ENT
CONFIGURATION
SET UP
IN / OUT
PUMP CALIBRATION
DOSING MODE
SET UP
DOSING PUMP
UNITS
LOCK CODE
FLOWMETER
MODBUS
FLOWMETER
FREQUENCY
LOW
%
l / h
0 0 0
0 0 0
MODE
25.0
Change by pressing
and confirm by pressing
ENT
Change low (LOW) or high (HIGH) frequency by pressing
and confirm by pressing
ENT
Enter the desired password
and confirm by pressing
ENT
Pressing
ESC
for 3 seconds locks the pump