10
SLS/SLH 10/06
Parameters
Type
Min. Value
Max. Value
Default
R134A
unit
LS (low speed) only if STEP
HP1
bar 0 28 21 14
LP1
bar 0 16 11 7
DPSET (only if FSC)
bar 10 24 16 10
MINDP
(only if FSC)
bar 1 25 11
6
MIN Speed
(only if FSC)
Vdc 0 10 0
MAX Speed
(only if FSC)
Vdc 0 10 10
Condensation (cool)
MDP
bar
0 28 23.5 15
High
bar
0 28 24.5 18
Diff. bar
0
3
1
Condensation (heat)
Low
°C
0 99 15 15
High
°C
0 99 30 18
Min LWT
Limit
°C
-20
20
5.0
Diff.
°C
0.5
3
1.5
Max LWT
Limit
°C
20
55
47
Diff.
°C
0.5
10
3
Interlock enabled
Flag
N=NO
Y=YES
N
Phase control alarm enabled
Flag
N=NO
Y=YES
N
Delay time flowswitch alarm
running
1 20 1
start
-up
Sec 1 20 5
LOP
Se - point
bar
0
3
1.8 (1 x SLH)
Diff.
bar
0
3
1
Delay LOP alarm
running
Sec 0 120 45
start -up
Sec
0
120
60
Diff pressure
Alarm enabled
Flag
N=NO
Y=YES
Y
Delay rating
Sec
0
120
60
Set - point
bar
2
10
6
Diff. bar
2
10
0
Antifreeze
Limit °C
-15
10
4
Diff.
°C 0 99 2
Antifreeze heater
Set-point °C -15 10 5
Diff. °C
0
99
2
Recovery antifreeze
Limit °C
-15
10
3
Diff.
°C 0 99 2
Recovery antifreeze heater
Set-point °C -15 10 5
Diff.
°C 0 99 2
Digital input
DI 15/16
Function Unload
Summary of Contents for SLS-SLH
Page 1: ...Chiller unit SLS SLH...