9
SLS/SLH 10/06
Parameters
Type
Min. Value
Max. Value
Default
R134A
unit
TMAX °C
-20
50
30
TMIN
°C
-20
50
+5
DELTA-V
Volt
0.0 5.0 5.0
Cool setpoint 2
Return
mCS+2
20
14
Outlet
mCS
20
12
Heat setpoint 2
Return
20
mHS-2
40
Outlet
20
mHS
42
HEAT SET comp.
Flag N=NO
Y=YES
N
Set -point
°C
-999.9
999.9
5.0
Diff.
°C
-999.9
999.9
-005.0
Max.
°C
-999.9
999.9
-005.0
COOL SET comp.
Flag N=NO
Y=YES
N
Set -point
°C
-999.9
999.9
24.0
Diff.
°C
-999.9
999.9
10.0
Max.
°C
-999.9
999.9
-002.0
Serial Card
Flag
N=NO
Y=YES
N
GSM modem
Flag
N=NO
Y=YES
N
ChillerNet
Flag N=NO
Y=YES
N
Water temperature
RWT - P
Type control
Flag
RWT P+I
LWT
RWT P
RWT P+I
Sec
0
999
600
Min.time on
compressor
Sec 0 999
300
Min.time off
compressor
Sec 0 999
300
Loading time
compressor
Sec 0 999 20
Unloading time
compressor
Sec 0 999 15
Min.cooling
setpoint (mCS)
°C
-10
9.9
6
Max. heating
setpoint (MHS)
°C
20
55
50
Pump management
Remote logic
Flag
N=NO
Y=YES
N
Stand-by
hour
1 24
00h
Delay OFF
Sec
0
60
20
Minimum time between pump/compressor
Sec 0 60 30
Pump down
Enable Flag
N=NO
Y=YES
Y
Maximum time
Sec
5
90
15
Set SP
bar
0.2
3
1.8
Condensation
type control
Flag
STEP
FSC
STD:
STEP
(note 1)
LAK:
FSC
Delay start
fans
Sec
-10
10
00
LS (low speed) only if STEP
Set-point °C -20 00 00
Diff..
°C 0 99 30
Summary of Contents for SLS-SLH
Page 1: ...Chiller unit SLS SLH...