3.4. Hot water connection
Connect the hot water pipe to the heater's hot water connection
(red) using a flat gasket
1
or compression fitting
2
.
1
2
3.5. Cold water connection
Tip
When installing the heater, you need a safety group. The safety
group and associated fittings are not included in the package.
The safety group must be suitable for a water pressure level of
up to 800 kPa.
a) Connect the cold water pipe to the heater's cold water
connection (blue) using a flat gasket
1
or compression fitting
2
.
1
2
b) Mount a safety group approved for use in the country of
installation to the cold water pipe. When doing so, please note
the following instructions:
-
Position the safety group so the flow direction is either
horizontal or vertical from bottom to top.
-
The expansion outlet of the safety group should face
downwards.
-
The expansion outlet of the safety group must remain
unobstructed. Only the funnel may be connected to the
expansion outlet. Do not connect a hose or pipe to the
expansion outlet.
-
The length of the hose between the safety group and the
water heater should be no more than 2 metres.
ä
Caution!
Take note of the direction in which the water flows through the
safety group. The direction is indicated by an arrow on the safety
group.
c) Connect the funnel's expansion outlet to the home's drainage
system.
13
Summary of Contents for Smartboiler Mono
Page 1: ...A Itho Daalderop Smartboiler Installation Use ...
Page 2: ...Translation of the original document ...
Page 37: ...37 ...