APT3100
Smart Pressure Transmitter
Operation Manual M3100-EO1G
10
Duon System Co.,Ltd.
2.10 Installation of Explosion Protected Type Transmitters
2.10.1 KOSHA Certification
Caution for KOSHA Flameproof is following type.
[Note1] Model APT3100 diaphragm sealed for potentially explosive atmosphere:
z
Type of Protection and Marking Code: Ex d
Ⅱ
C T6
z
Temperature Class: T6
z
Ambient Temperature: -20 ~ 60'C
z
Process Temperature: Max. 80'C
[Note2] Electrical Data
z
Supply Voltage: Maximum 45 Vdc
z
Output signal: 4 ~ 20mA, maximum 22mA
[Note3] Installation
z
All wiring shall comply with local installation requirement.
z
The cable entry devices shall be of a certified flameproof type, suitable for conditions of
use.
[Note4] Operation
z
Wait one minute after power -disconnection, before opening the enclosure.
z
Take care not to generate mechanical spark when access to the instrument and peripheral
devices in hazardous location.
[Note5] Maintenance and Repair
z
The instrument modification or parts replacement by other than authorized representative
of DUON System is prohibited and will void KOSHA Flameproof.
2.10.2 KEMA / ATEX Certification
ATEX Certification number : KEMA07ATEX0103
CE 0344
II 2 G
Note 1. Model APT3100 for potentially explosive atmosphere
z
Ex d IIC T6...T4
z
Operating Temperature : -20
℃
≤
T
amb
≤
+60
°
C
z
T6 for process
≤
85
°
C;
z
T5 for process
≤
100
°
C;
z
T4 for process
≤
130
°
C;