Tab. 4.2.1.2 Communication ports
Environmental phenom-
ena
Test specification
Description
Basic standard
Acceptance
criteria
Conducted disturbance
induced by radio-
frequency fields
Frequency sweep
PN-EN 61000-4-6
A
0,15-80 MHz
Frequency range
10 V
r.m.s.
80 %AM (1kHz)
Amplitude Modulated
150 Ω
Source impedance
Spot frequencies
27 MHz, 68 MHz
Frequencies
10 V
r.m.s.
80 %AM (1kHz)
Amplitude Modulated
150 Ω
Source impedance
100 %
Duty cycle
Fast transient – Zone A
5/50 ns
Tr/Th
PN-EN 61000-4-4
B
5 kHz
Repetition frequency
2 kV
Peak voltage
Slow damped oscillatory
wave
1 MHz
Voltage oscillation frequency
PN-EN 61000-4-
12
B
75 ns
Tr - Voltage rise time
400 Hz
Repetition frequency
200 Ω
Output impedance
0 kV
Differential mode - peak voltage
1 kV
Common mode - peak voltage
Surge - Zone A
1,2/50 (8/ 20) µs
Voltage (current) rise time / time to half
value Tr /Th
PN-EN 61000-4-5
B
4 kV
Line-to-earth
2 Ω
Source impedance
Tab. 4.2.1.3 Auxiliary power supply port
Environmental pheno-
mena
Test specification
Description
Basic standard
Acceptance
criteria
Conducted disturbance
induced by radio-
frequency fields
Frequency sweep
PN-EN 61000-4-6
A
0,15-80 MHz
Frequency range
10 V
r.m.s.
80 %AM (1kHz)
Amplitude Modulated
150 Ω
Source impedance
Spot frequencies
27 MHz, 68 MHz
Frequencies
10 V
r.m.s.
80 %AM (1kHz)
Amplitude Modulated
150 Ω
Source impedance
100 %
Duty cycle
Fast transient – Zone A
5/50 ns
Tr/Th
PN-EN 61000-4-4
B
5 kHz
Repetition frequency
4 kV
Peak voltage
Slow damped oscillatory
wave
1 MHz
Voltage oscillation frequency
PN-EN 61000-4-
12
B
75 ns
Tr - Voltage rise time
400 Hz
Repetition frequency
200 Ω
Output impedance
1 kV
Differential mode - peak voltage
2,5 kV
Common mode - peak voltage
Surge - Zone A
1,2/50 (8/ 20) µs
Voltage (current) rise time / time to half
value Tr /Th
PN-EN 61000-4-5
B
2 kV
Line-to-line
4 kV
Line-to-earth
2 Ω
Source impedance
A.C. and D.C. voltage
dips and voltage inter-
ruption
0% corresponds to the
complete reduction of
supply voltage
0 %
during ≤ 0,5 i 1 periods A.C. or ≤ 50 ms
D.C.
PN-EN 61000-4-
11
PN-EN 61000-4-
29
A
C
(for time
longer than
specified)
40 %
during ≤ 10 periods A. C. or ≤ 200 ms D.C.
70 %