PS200 Configuration & Operation Guide
APPENDIX A-3 PARAMETER LISTING
Page 118
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 03
STATUS WORDS
Description
x
x
x
3.01
Main Ctrl Word
Digital communication Control Word as received from control system
x
x
x
3.02
Main Status Word
Drive status word that is issued to control system
x
x
x
3.03
Aux Status Word
Not Used PS200 Logic
x
x
x
3.04
Limit Word 1
Not Used PS200 Logic
x
x
x
3.05
Fault Word 1
Drive Fault Words
x
x
x
3.06
Fault Word 2
Drive Fault Words
x
x
x
3.07
System Fault
System Fault Words
x
x
x
3.08
Alarm Word 1
Drive Alarm Words
x
x
x
3.09
Alarm Word 2
Drive Alarm Words
x
x
x
3.10
PS Alarm Words
PumpSmart Pump Protection Alarms
x
x
x
3.11
PS Condition Words
PumpSmart condition monitoring words
Group 03
Parameter
STATUS
WORD
BIT
NAME
VALUE
Description
0
Reserved
1
Enabled
1
ENABLE
0
Coast to stop
2
Reserved
1
Start
3
START/STOP
0
Stop according to parameter 12.08 STOP FUNCTION
4
Reserved
5
Reserved
6
Reserved
7
Reserved
8
RESET FAULT
0
o
1
Reset drive / pump fault
3.01
MAIN CTRL
WORD
9 - 15
Reserved
Group 03
Parameter
STATUS
WORD
BIT
NAME
VALUE
Description
1
Ready to start
0
READY
0
Initialising or initialising error
1
Enabled
1
ENABLE
0
Coast to stop
2
Reserved
1
Running with selected Setpoint
3
RUNNING
0
Stopped
4
Reserved
1
Drive in remote mode
5
REMOTE
0
Drive in local mode
6
Reserved
1
Drive at Setpoint
7
AT_SETPOINT
0
Drive not at Setpoint
1
A fault is active
8
FAULTED
0
No faults active
1
A warning is active
9
WARNING
0
No warning are active
1
Drive at a limit
10
LIMIT
0
Drive not at a limit
3.02
MAIN
STATUS
WORD
11-15
Reserved
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......