PS200 Configuration & Operation Guide
APPENDIX A-3 PARAMETER LISTING
Page 124
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 13
RAMPS
Description
X
X
X
13.01
ACCEL TIME
Defines the fast acceleration time (Range = 0 – 1800 sec). Default = 5 sec. Pre-
populated by setting of 11.03 MODE SELECT.
X
X
X
13.02
DECEL TIME
Defines the fast deceleration time (Range = 0 – 1800 sec). Default = 5 sec. Pre-
populated by setting of 11.03 MODE SELECT.
X
X
13.03
P-GAIN
Defines the proportional gain for the PID regulator (range 0 – 100). Defaults
based on control modes are Pressure= 0.5, Flow= 0.2, Pressure/Flow quadratic=
0.5, Level/Temperature= 2.5. Pre-populated by setting of 11.03 MODE SELECT.
X
X
13.04
I-TIME
Defines the integral time for the PID regulator (range 0 – 320). Defaults based on
control modes are Pressure= 0.75, Flow= 1.75, Pressure/Flow quadratic= 3.0,
Level/Temperature= 0.75. Pre-populated by setting of 11.03 MODE SELECT.
X
X
13.05**
D-TIME
Defines the derivation time of the PID regulator (range = 0 – 10 sec). Default = 0
deactivates the “D” time
X
X
13.06**
PID DERIV FILTER
Defines the constant of the filter used to smooth the derivation component of the
process PID regulator (range = 0.04 – 10 sec). Default is 1 sec.
X
X
13.07**
PID INTEGRATION
Activates the integration function of the PID regulator. Choices are ‘ON” (default)
and “OFF”.
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 14
SPD LIM/STRT LVL
Description
X
X
X
14.01
MAXIMUM SPEED
Defines the allowable maximum speed. Default setting is parameter 11.07
MOTOR FL RPM.
X
X
X
14.02
MINIMUM SPEED
Defines the minimum speed range. Default setting is 25% of parameter 11.07
MOTOR FL RPM.
X
X
X
14.03
MAXIMUM FREQUENCY
Defines the maximum allowable frequency when operating in scalar mode. This
parameter is not shown unless parameter 11.09 MOTOR CTRL MODE is set to
SCALAR. Default setting is parameter 11.06 MOTOR NOM FREQ.
X
X
X
14.04
MINIMUM FREQUENCY
Defines the minimum allowable frequency when operating in scalar mode. This
parameter is not shown unless parameter 11.09 MOTOR CTRL MODE is set to
SCALAR. Default setting is 25% of parameter 11.06 MOTOR NOM FREQ.
CONFIG SPEED MIN
Defines the reaction of the drive when the PS200 tries to regulate at a speed at or
below 14.02 MINIMUM SPEED.
SPD = MINSPD
The PS200 will stay at this speed until the transient clears or unit is manually
shutdown; unless a fault occurs.
X
X
X
14.05
SPD = 0
[default]
The drive will stay at minimum speed until 14.06 STP DELAY MIN SPD times-out
and then it will shutdown.
X
X
14.06
STP DELAY MIN SPD
The time period the drive will stay at 14.05 MINIMUM SPEED before stopping.
Range = 0 –1800 sec. (Single pump macro default = 0 sec, Multi-pump macro
default =3 sec). Functions when 14.05 is set to SPD=0. Becomes active if
setpoint would result in regulation below min speed, closed valve condition in
pressure control and Secondary Protect A & B.
X
X
14.07
RESTART VALUE
If the drive is shutdown by 14.05 CONFIG SPEED MIN due to no system demand
(pressure control only) the drive will sleep until the process actual value drops
below a set 14.07 RESTART VALUE for longer than 14.08 RESTART DELAY. If
operating in inverse mode (21.01) the drive will sleep until the process variable
rises above the restart value. Wake-up level in % of setpoint value = 0 – 150%. To
disable the Restart Value function in both normal and inverse settings enter
“0%”. 12.02 AUTO RESTART does not influence the restart function. Default = 0.
X
X
14.08
RESTART DELAY
Time delay for 14.07 RESTART VALUE. Range = 0 –1800 sec. Default = 0 seconds
X
X
X
14.09
PRIMING DELAY
Setting range is 0-6000 sec. When the drive is starting from 0 RPM this parameter
delays pump protection faults (23.01,07,11, 25.01,06, 07, 11,13, 15) for the
setting time. Default is “0”. Once the priming delay time is complete, 25.03
PROTECTION DELAY becomes functional. During the priming delay the pump runs
at 14.01 MAXIMUM SPEED since it cannot achieve the setpoint.
X
14.10
CRITICAL SPEED 1
Value range: 0-9999 Rpm. Default is “0”. If setting of CRITICAL SPEED 1 = “0”
then the Critical Speed functionality is disabled.
X
14.11
CRITICAL SPEED 2
Value range: 0-9999 rpm. Default is “0". If setting of CRITICAL SPEED 2 = “0”
then the Critical Speed functionality is disabled.
X
14.12
NCR WIDTH
Value Range: 0-1000 Rpm. Default is “0”. This is the total critical speed
bandwidth (½ above and ½ below) of the value set for Critical Speed 1 and 2. If
the setpoint falls in the critical speed zone the drive runs at a setpoint just above
or below the critical speed envelope if slowing down or ramping up to the
setpoint, respectively.
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......