PS200 Configuration & Operation Guide
APPENDIX A-3 PARAMETER LISTING
Page 129
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 18
AI EXT MODULE
Description
X
X
X
18.01
XTAI1
Selections are VIB 1, VIB 2, COND 1 or COND 2. Default is “Not Used”. (MUST BE
A LINEAR SIGNAL)
X
X
X
18.02
XTAI2
Selections are VIB 1, VIB 2, COND 1 or COND 2. Default is “Not Used”. (MUST BE
A LINEAR SIGNAL)
MINIMUM XT AI1
Defines the value for analog input XT AI1. Note: parameter 30.02 AI/O EXT
MODULE must be set to RAIO Slot 1 or Slot 2.
0 MA
Do not use. A 0-mA signal will activate a Sensor Failure fault function unless
24.01 and 24.02 are disabled.
4 MA
[default]
4 mA is selected as the minimum value.
TUNED VALUE
Select tuned value after the tune function has been completed. This will select the
tuned value for the minimum value of XT AI1.
X
X
X
18.03
TUNE
This parameter sets the minimum value of the signal to be applied to XT AI1.
When tune is selected and enter is pressed the tuned value for XT AI1 is set to the
actual XT AI1 value when the tune function was activated. This function is useful
for zeroing out any system hysteresis.
MAXIMUM XT AI1
Defines the maximum value for analog input XT AI1.
20 MA
[default]
Maximum scaled setting is at 20 MA
TUNED VALUE
Select tuned value after the tune function has been completed. This will select the
tuned value for the maximum value of XT AI1.
X
X
X
18.04**
TUNE
This parameter sets the maximum value of the signal to be applied to XT AI1.
When TUNE is selected and ENTER is pressed the tuned value for XT AI1is set to
the actual XT AI1 value when the tune function was activated. This function is
useful for zeroing out any system hysteresis.
X
X
X
18.05**
SCALE XT AI1
Scales XT AI1. Default = 100%
X
X
X
18.06**
FILTER XT AI1
Defines the filter time constant for XT AI1. Default is 0.1 sec. Note the signal is
also filtered due to the signal interface hardware (10ms time constant). This
cannot be changed by any parameter.
INVERT XT AI1
Activates/deactivates the inversion of analog input signal XT AI1.
NO
No inversion
X
X
X
18.07**
YES
Inversion is active. The maximum value of the analog input signal (20 mA)
corresponds to the minimum vibration or condition level and the minimum value
of the analog input signal (4 mA) corresponds to the maximum vibration or
condition value.
MINIMUM XT AI2
Defines the value for analog input XT AI2. Note: parameter 30.02 AI/O EXT
MODULE must be set to RAIO Slot 1 or Slot 2.
0 MA
Do not use. A 0-mA signal will activate a Sensor Failure fault function unless
24.01 and 24.02 are disabled.
4 MA
[default]
4 mA is selected as the minimum value.
TUNED VALUE
Select tuned value after the tune function has been completed. This will select the
tuned value for the minimum value of XT AI2.
X
X
X
18.08
TUNE
This parameter sets the minimum value of the signal to be applied to XT AI2.
When tune is selected and enter is pressed the tuned value for XT AI2 is set to the
actual XT AI2 value when the tune function was activated. This function is useful
for zeroing out any system hysteresis.
MAXIMUM XT AI2
Defines the maximum value for analog input XT AI2.
20 MA
[default]
Maximum scaled setting is at 20 MA
TUNED VALUE
Select tuned value after the tune function has been completed. This will select the
tuned value for the maximum value of XT AI2.
X
X
X
18.09**
TUNE
This parameter sets the maximum value of the signal to be applied to XT AI2.
When TUNE is selected and ENTER is pressed the tuned value for XT AI2 is set to
the actual XT AI2 value when the tune function was activated. This function is
useful for zeroing out any system hysteresis.
X
X
X
18.10**
SCALE XT AI2
Scales XT AI2. Default = 100%
X
X
X
18.11**
FILTER XT AI2
Defines the filter time constant for XT AI2. Default is 0.1 sec. Note the signal is
also filtered due to the signal interface hardware (10ms time constant). This
cannot be changed by any parameter.
INVERT XT AI2
Activates/deactivates the inversion of analog input signal XT AI2.
NO
No inversion
X
X
X
18.12**
YES
Inversion is active. The maximum value of the analog input signal (20 mA)
corresponds to the minimum vibration or condition level and the minimum value
of the analog input signal (4 mA) corresponds to the maximum vibration or
condition value.
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......