PS200 Configuration & Operation Guide
APPENDIX A-3 PARAMETER LISTING
Page 136
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 24
FAULT FUNCTIONS
Description
DIGIT RST CONFIG
Allows drive faults to be reset using an external switch wired into DI6 if condition
that caused the fault has been corrected.
PUMP FAULTS
Resets pump faults: PUMP PROTECT, LOW DEMAND, DRY RUN, MIN FLOW, VIB 1
AND 2, COND 1 and 2 and PROCESS SENSOR.
VFD FAULTS
Resets a keypad fault or VFD fault
X
X
X
24.04
BOTH
[default]
Resets both Pump faults and VFD faults.
X
X
X
24.05**
MOTOR THERM PROT
Selects how the drive reacts when the motor overtemperature is detected by the
function defined by parameter 24.06 MOTOR THERM P MODE. Default =
WARNING. Other choices: FAULT, NOT SELECTED.
X
X
X
24.06**
MOTOR THERM P MODE
Selects the thermal protection mode of the motor. When overtemperature is
detected the drive reacts as defined by parameter 24.05 MOTOR THERM PROT.
Default = DTC. Other choices: USER MODE and THERMISTOR. Thermistor is wired
into DI-4. Automatically updates to THERMISTOR when thermistor is selected in
parameter 25.06.
X
X
X
24.07**
MOTOR THERM TIME
Defines the thermal time constant for the user defined thermal model.
X
X
X
24.08**
MOTOR LOAD CURVE
Defines the load curve together by parameters 24.09 ZERO SPEED LOAD and
24.10 BREAK POINT. The load curve is used in the user defined thermal model.
X
X
X
24.09**
ZERO SPEED LOAD
Defines the load curve together by 24.08 and 24.10.
X
X
X
24.10**
BREAK POINT
Defines the load curve together by 24.08 and 24.09.
X
X
X
24.11**
STALL FUNCTION
Selects how the drive reacts to a motor stall condition. Default = NOT SEL. Other
choices: WARNING, FAULT.
X
X
X
24.12**
STALL FREQ HI
Defines the frequency limit for the stall function.
X
X
X
24.13**
STALL TIME
Defines the time for the stall function.
X
X
X
24.14**
UNDERLOAD FUNC
Selects how the drive reacts to underload. Default = NOT SEL.
Other choices: WARNING or FAULT.
X
X
X
24.15**
UNDERLOAD TIME
Time limit for the underload function.
X
X
X
24.16**
UNDERLOAD CURVE
Selects the load curve for the underload function.
X
X
X
24.17**
MOTOR PHASE LOSS
Activates the motor phase loss supervisory function. Default = NOT SEL. Other
choices: FAULT.
X
X
X
24.18**
GROUND FAULT
Selects how the drive reacts when an earth fault is detected in the motor or the
motor cable. Default = FAULT. Other choice: WARNING.
X
X
X
24.19**
COMM FLT FUNC
Selects how the drive reacts in a fieldbus comm break i.e; if the drive fails to
receive the main ref data set or the aux ref data set. The time delays are given by
parameters 24.20 and 24.21. Default = LAST SPEED. Other choices: NOT
SELECTED, FAULT.
X
X
X
24.20**
MAIN REF DS T-OUT
Defines the time delay for the main ref data set supervision. Default = 3 Sec
X
X
X
24.21**
AUX DS T- OUT
Defines the time delay for the aux ref data set supervision. Default = 3 Sec
X
X
X
24.22**
IO CONFIG FUNC
Selects how the drive reacts in case of improper selection of the I/O. Default =
NOT SEL. Other choice: WARNING.
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......