PS200 Configuration & Operation Guide
APPENDIX A-3 PARAMETER LISTING
Page 137
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 25
PUMP PROTECT
Description
PUMP PROTECT CTRL
Actual process value is lower than 25.02 PROTECTION LIMIT for 25.03
PROTECTION DELAY and the PS200 is at maximum speed for the protection delay.
DISABLED
[default]
Protection is disabled
ALARM
The PS200 generates a warning only “PUMP PROTECT”. Relay outputs may be
configured to changed. No other action is taken.
X
X
25.01
ALARM AND CONTROL
The PS200 generates a warning “Pump Protect” and controls according to the
setting of 14.05 CONFIG SPEED MIN.
X
X
25.02
PROTECTION LIMIT
This is the value, in % of the setpoint, at which 25.01 PUMP PROTECT CTRL
activates when pump is at max speed for the protection delay.
Setting range: 0 – 100% of setpoint. The default setting is 97%.
X
X
X
25.03
PROTECTION DELAY
This is the period prior to the activation of 25.01 PUMP PROTECT CTRL. Also
applies to SECONDARY PROTECT A/B, MIN FLOW, DRY RUN and RUNOUT CTRL.
Setting = 0 – 200 sec. Default: 0 seconds.
X
X
X
25.04
ERROR RESET
Indicates number of fault resets. Parameter 12.02 AUTO RESTART must be set to
“ON”. Selection range is 0 – 19. Default is “0”. When set to “0” ERROR RESET is
disabled. Time between resets is set by 25.05 RESET DELAY. Manual intervention
is required if fault is still active after set number of resets has been achieved. The
drive reaction to the fault will be according to 14.05 CONFIG SPEED MIN. Reset
action is applicable to parameters 25.01, 25.11 and 25.15.
X
X
X
25.05
RESET DELAY
The period of time that the PS200 will wait after an alarm and control condition
before attempting an error reset. Setting Range: 250 sec. Default: 60 sec.
SECONDARY PROTECT A
Loss of digital input 4 (DI4) for 25.03 PROTECTION DELAY.
DISABLED
[default]
Protection is disabled
ALARM
The PS200 generates a warning only “SECONDARY PROTECT A”. Relay outputs
may be configured to change. No other action is taken.
ALARM AND CONTROL
The PS200 generates a warning “SECONDARY PROTECT A”and controls according
to the setting of 14.05 CONFIG SPEED MIN. Parameter 12.02 AUTO RESTART must
be set to “ON” to automatically restart once fault has been reset.
X
X
X
25.06
THERMISTOR
Allows the use of a motor thermistor at DI4. Parameter 24.06 MOTOR THERM P
MODE is automatically updated to "THERMISTOR".
SECONDARY PROTECT B
Loss of digital input 5 (DI5) for 25.03 PROTECTION DELAY.
DISABLED
[default]
Protection is disabled
ALARM
The PS200 generates a warning only “SECONDARY PROTECT B”. Relay outputs
may be configured to change. No other action is taken.
X
X
X
25.07
ALARM AND CONTROL
The PS200 generates a warning “SECONDARY PROTECT B” and controls according
to the setting of 14.05 CONFIG SPEED MIN. Parameter 12.02 AUTO RESTART
must be set to “ON” to automatically restart once fault has been reset.
X
X
X
25.08
BEP POWER
Value range setting is 0 – 9999. Defines the power at best efficiency point of the
pump. The default is 90% of the 11.08 MOTOR NOM POWER.
X
X
X
25.09
PWR OFFSET
Value range setting is -20.0 to +20.0. This is a mechanical power loss offset value
(e.g. seal losses). Default = 0.
X
X
X
25.10
BEP SPEED
Value range setting is 0 – 9999. Defines the pump speed associated with the BEP
power. The default is 11.07 MOTOR FL RPM.
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......