PS200 Configuration & Operation Guide
SINGLE PUMP PROCESS
Page 18
AI2 MIN - This is the process value that corresponds to the
transmitter's minimum signal [4 mA]. This value is normally zero
on a pressure or flow transmitter. Refer to your transmitter
calibration sheet, or the instrument nameplate, for this value.
NOTE - Most pressure and flow transmitters are configured for a
reading of 0 [PSIG, GPM, etc…] at 4 mA. If so, this step may be
omitted since the default of parameter 16.04 is 0.
16.04 AI2 MIN
KEY SEQUENCE
[From parameter group: 16.03 AI2 MAX]
OR
Scroll to parameter 16.04
AI2 MIN
ENTER
Press to enter the
parameter setting mode
OR
OR
Use a combination of the
arrow keys to scroll to the
correct value. Example
shown - 0 PSIG
Enter the reading of the
primary process
transmitter that
corresponds to its 4-mA
signal.
If your transmitter signal
is zero (0) at 4mA, skip
to the next section
(Enter Setpoint).
Units are the same as
entered in 15.01.
ENTER
Press to complete the
entry
ACT
PAR
FUNC
DRIVE
ENTER
1 L
Æ
0 P S I G 0
1 6 S E T P O I N T S E L E C T
4 A I 2 M I N
0