PS200 Configuration & Operation Guide
MULTI PUMP-PROCESS CONFIGURATION
Page 33
11.07 MOTOR FL RPM
KEY SEQUENCE
[From parameter: 11.05 MOTOR NOM
CURRENT]
OR
Scroll to parameter 11.07
“MOTOR FL RPM”
ENTER
Press to enter the
parameter setting mode
OR
OR
Use a combination of the
arrow keys to scroll to the
nameplate full load speed.
Enter the full load RPM
of the motor. Please
note this is the
nameplate value of the
full load RPM and not
the nominal speed of
the motor.
For Example: An 1800 RPM
motor might have a full
load RPM of 1770 RPM
ENTER
Press to complete the
entry
11.08 MOTOR NOM POWER
KEY SEQUENCE
[From parameter: 11.07 MOTOR FL RPM]
OR
Scroll to parameter
11.08 “MOTOR NOM
POWER”
ENTER
Press to enter the
parameter setting
mode
OR
OR
Use a combination of
the arrow keys to scroll
to the nameplate
power.
Enter the nominal power
(HP or kW) of the motor
as found on the motor
nameplate.
If you are using the
Default language of
ENGLISH(AM), then the
units of entry will be
Horsepower. Otherwise
kW will be the units of
entry.
ENTER
Press to complete the
entry
ACT
PAR
FUNC
DRIVE
ENTER
1 L
Æ
0 P S I G 0
1 1 S T A R T - U P D A T A
7 M O T O R F L R P M
1770
ACT
PAR
FUNC
DRIVE
ENTER
1 L
Æ
0 P S I G 0
1 1 S T A R T - U P D A T A
8 M O T O R N O M P O W E R
50
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......