PS200 Configuration & Operation Guide
MULTI PUMP-PROCESS CONFIGURATION
Page 39
PROCESS TRANSMITTER CONFIGURATION
The primary process transmitter is the device that will
measure your process conditions using a 4-20 mA signal. The
PS200 requires information to properly scale this signal.
AI2 MAX - This refers to the process value that your
transmitter is calibrated to at its max signal [20 mA]. Refer to
your transmitter calibration sheet, or the instrument
nameplate, for this value.
Example - a direct reading flowmeter [e.g. magmeter,
vortex flowmeter, etc…] that has a range of 0 - 2000
GPM would be calibrated such that at 2000 GPM, the
output of the transmitter would be 20 mA. Parameter
16.03 would be set to 2000 in this case. The units of
16.03 are the same as selected in parameter 15.01,
although they are not displayed
NOTES
Differential pressure flowmeters [e.g. orifice plate,
venturi] do not produce 4-20 mA signals that are linear
with the flow-rate. PumpSmart refers to this as a
QUADRATIC input -- Refer to the section DIFFERENTIAL
FLOWMETERS in the options section for proper setup.
16.03 AI2 MAX
KEY SEQUENCE
[From parameter group: 15.01 AI2 UNIT]
OR
Scroll to parameter group
16 SETPOINT SELECT
OR
Scroll to parameter 16.03
AI2 MAX
ENTER
Press to enter the
parameter setting mode
OR
OR
Use a combination of the
arrow keys to scroll to the
correct value. Example
shown - 2000 GPM
Enter the reading of the
primary process
transmitter that
corresponds to its 20
mA signal.
Units are the same as
entered in 15.01
ENTER
Press to complete the
entry
ACT
PAR
FUNC
DRIVE
ENTER
1 L
Æ
0 P S I G 0
1 6 S E T P O I N T S E L E C T
3 A I 2 M A X
2000
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......