PS200 Configuration & Operation Guide
OPTIONS & FEATURES
Page 72
Analog Outputs
The PumpSmart PS200 has two 4-20 mA analog outputs as standard, with an additional two outputs available
with the optional RAIO-01 module. These outputs may be configured by the user to output from a selection of
eleven actual signals. Parameter group 20 is used to configure these outputs. Reference the detailed wiring
diagrams in the appendix.
Parameter
Name
Value/Range
Note
20.01
ANALOG OUT 1
NOT USED
[default]
SPEED
FREQUENCY
CURRENT
TORQUE
POWER
VIBR LVL 1
VIBR LVL 2
COND LVL 1
COND LVL 2
PROC VAR
ENERGY SAVNG
Refer to Appendix A-3 PARAMETER
LISTING for default scaling values for
each selection.
20.06
ANALOG OUT 2
NOT USED
[default]
SPEED
FREQUENCY
CURRENT
TORQUE
POWER
VIBR LVL 1
VIBR LVL 2
COND LVL 1
COND LVL 2
PROC VAR
ENERGY SAVNG
Refer to Appendix A-3 PARAMETER
LISTING for default scaling values for
each selection.
20.11
XT ANALOG OUT AI1
Note – This selection
requires the optional
RAIO-01 module AND
parameter 30.02 AI/O
MODULE set to slot #
module is mounted in.
NOT USED
[default]
SPEED
FREQUENCY
CURRENT
TORQUE
POWER
VIBR LVL 1
VIBR LVL 2
COND LVL 1
COND LVL 2
PROC VAR
ENERGY SAVNG
Refer to Appendix A-3 PARAMETER
LISTING for default scaling values for
each selection.
20.16
XT ANALOG OUT AI2
Note – This selection
requires the optional
RAIO-01 module AND
parameter 30.02 AI/O
MODULE set to slot #
module is mounted in.
NOT USED
[default]
SPEED
FREQUENCY
CURRENT
TORQUE
POWER
VIBR LVL 1
VIBR LVL 2
COND LVL 1
COND LVL 2
PROC VAR
ENERGY SAVNG
Refer to Appendix A-3 PARAMETER
LISTING for default scaling values for
each selection.
26.03
SAVINGS SCALE
0-999999
10000
[default]
If ENERGY SAVNG is selected as an
output, this parameter must be set to
scale the signal. 4 mA = $0.00 and 20
mA equals this amount. For example
20 mA = $10,000.
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......