PS200 Configuration & Operation Guide
OPTIONS & FEATURES
Page 79
Any parameter changes that are made using a Fieldbus control system must be saved to the drive.
Parameter
Name
Value/Range
Note(s)
10.04
PARAMETER SAVE
DONE
[default]
SAVE
Parameters that are manually entered
through the keypad are automatically
saved, only parameters entered through
a Fieldbus connection must be saved.
To save, select SAVE and press the
ENTER key or write to parameter 10.04
using digital communication to SAVE.
Language
The PumpSmart system fully supports 6 languages; English (AM), French, German, Italian, Portuguese and
Spanish. Portions of the PumpSmart parameters are also available in Dutch, Danish, Finnish, Swedish, Czech, and
Polish.
English(AM) refers to American English and is the default language. Units of power are in HP. English without the
(AM) notation refers to British English, with units of power in kW.
Parameter
Name
Value/Range
Note(s)
11.01
LANGUAGE
ENGLISH
ENGLISH(AM)
DEUTSCH
ITALIANO
ESPANOL
PORTUGUESE
NEDERLANDS
FRANCAIS
DANSK
SUOMI
SVENSKA
CESKY
POLSKI
ENGLISH (AM) is default setting
Lead-Lag Switching
Automatically alternating the Lead-Lag responsibilities of the drives in multi-pump control may be accomplished
by setting the parameter 22.05 SWITCH LEAD LAG to the desired switching period. The lead-lag switch will occur
based upon the number of hours the unit has been running.
NOTE - This function may be tested by setting the value to 0.1 hr (6 minutes).
Parameter
Name
Value/Range
Note(s)
22.05
SWITCH LEAD
0-4000 Hours
48
[default]
This is the number of hours that a pump
is running before switching the LEAD
designation to the next pump.
Setting “0” disables the switching
function, including automatic switching
during a drive or pump protection fault.
22.12
MANUAL SWITCH
1
2
3
4
DISABLED
[default]
This parameter manually switches the
lead status to the selected pump. This
function is through the MASTER drive
keypad only.
Summary of Contents for PumpSmart PS200
Page 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Page 2: ......
Page 4: ......
Page 8: ......
Page 26: ......
Page 72: ......
Page 105: ......
Page 119: ......
Page 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Page 147: ......
Page 158: ......