a. Cover Removal and Installation Procedure

• Using a flathead screwdriver, unscrew the four

cover screws and remove the electrical connec-
tion cover (A).

• Place electrical connection cover on the flow

switch and insert four cover screws. Tighten the
screws to 10 lb•in (1.13 N•m).

STEP 4 - Electric Wire Connections

• To prevent electrical shock, turn off the electrical power before making electrical connections.

• To prevent an electrical fire or equipment damage, electrical wiring insulation must have a rating of 167˚F 

(75˚C) if the liquid’s temperature exceeds 180˚F (82˚C).

• To prevent electrocution, when the electrical power is connected to the flow switch, do not touch the 

terminals.

• Make sure flow switch electrical cover is secured before turning on electric power.

Failure to follow this warning could cause property damage, personal injury or death.

!

WARNING

c.

Insert the flow switch into the pipe tee. Turn 
the flow switch two (2) or three (3) revolutions 
clockwise until tight. Do not put excessive 
force on cover when turning.

FLOW

d.

Place a 1 3/8" open end wrench on flow switch
body to tighten to final position. Final position 
is with arrow on body aligned in the same 
direction as liquid flow.

Teflon

®

 

b.

Apply pipe sealing compound or Teflon

®

tape to the 

flow switch pipe threads.

NOTE:

Do not apply sealant to first threads as this 

switch is grounded (earthed) via the pipe mounting.

Summary of Contents for McDonnell & Miller FS8-W Series

Page 1: ...cable codes and ordinances To prevent electrical shock turn off the electrical power before making electrical connections To prevent an electrical fire or equipment damage electrical wiring insulation...

Page 2: ...65 an anticipated system switch operation rate of less than once per 2 5 minutes and any one cycle greater than 3 seconds on and 3 seconds off For applications with loads 0 5 and 38mA power factors e...

Page 3: ...1 38 398 Factory or 21 2 65 Minimum 17 9 67 8 1 20 36 12 1 45 8 81 25 149 Maximum 71 3 270 4 78 1 46 59 2 224 3 97 1 21 565 Factory or 3 80 Minimum 24 2 91 6 1 05 32 16 4 62 1 71 22 230 Maximum 89 337...

Page 4: ...nt Adjustment 2 50 118 5 99 5 3 80 278 0 227 0 4 100 442 0 391 0 5 125 847 0 762 0 6 150 1440 0 1325 0 Series FS8 W K Factor b If the flow rate in the pipe exceeds the maximum adjustment on the Flow S...

Page 5: ...irection as fluid will flow Some system conditions that require more than 5 pipe diameters are high viscosity fluid and high fluid velocity The flow switch must be installed in the pump suction piping...

Page 6: ...cution when the electrical power is connected to the flow switch do not touch the terminals Make sure flow switch electrical cover is secured before turning on electric power Failure to follow this wa...

Page 7: ...used to actuate a signal alarm or other device when flow occurs connect the wire from that device to the N O contact Connect the Hot power supply wire to C terminal For No Flow Mode of Operation Fig...

Page 8: ...low switch to activate Measure flow rate and match with velocities shown in flow rate chart c Check to see if paddle moves freely Some system piping disassembly may be required 3 Flow Switch Does Not...

Reviews: