OM-2245 / Operation and Maintenance Manual
ITW GSE 4400 / 400 Hz. Generator Set
March 15, 2015
Chapter 1-3
Page 7
f)
After operation, the unit has to be turned off before removing the aircraft plug. Press the 28 VDC
Start/stop button
g) The aircraft cable can now be removed from the aircraft and placed at the cable rest position.
Note!
Please note that the 28 VDC Start/Stop button also functions as a Reset push button.
If, for some reason, the unit stops due to an error / failure, record the fault number and message and forward
this information to your maintenance personnel. If the fault is no longer active, press the Start/Stop/Reset to
reset the alarm and the unit.
3) ARU Default Factory Settings:
28 V Voltage (V):
28.0
28 V Compensation (V/600A):
0.0 (Set if GPU supplied with cable)
28 V Current Limit (A):
1500.0
Output Mode:
Simultaneous
Fan Control:
Normal
Plug Temperature:
Normally Open