Page 11
Operation and Maintenance
Envistar Compact
DSEC191101.01.EN
Continuous product development may give rise to specification changes without notice.
3.3 StarCooler cooling unit (code ACEC)
The cooling unit is equipped with a reciprocating compressor.
Function
Function COOL
The cooling compressor starts when potential-free contact closes from the con-
trol unit.
Interlocking
The compressor is interlocked across the ventilation unit. When the ventilation
unit stops, the potential-free connector opens for cooling mode and the
compressor stops.
Compressor protection
In the event of overcurrent, or if the safety circuit alarm trips the motor protec-
tion, the compressor stops, the connector for the sum alarm closes and alerts
the control unit.
In the event of an alarm, correct the fault and reset the protective motor switch.
NB:
The high pressure switch has a manual reset button.
The safety circuit alarm will trip in the event of two different faults.
• High pressure in the system, HP
• Low pressure in the system, LP
If the safety circuit alarm trips repeatedly, an authorised refrigeration service
company must be called in.
Electrical connection
The junction box contains the following:
• Motor circuit breaker
• Contactor
• Starting equipment
The junction box is mounted inside the cooling unit and has been internally pre-
wired and tested at the factory.