Page 28
Operation and Maintenance
Envistar Top 04-21
DSET.190501.01.EN
Continuous product development may give rise to specification changes without notice.
5.6 Cooling Status – Cooling unit, size (code TEC) 16-21
With control equipment (code MX).
Status information is read on the Climatix display.
Information
Value/example
Explanation
Cooling unit status
Unit ON
Normal status for cooling mode if the
compressor is running depends on the cooling
load.
OFFbyALR
Switched off caused by alarm.
OFFbyDIN
Switched off due to interlock. Climatix interlocks
cooling operation.
OFFbyKey
Switched off due to Carel’s ON/OFF menu.
High cond. temp. The compressor’s speed is limited due to high
pressure.
Cooling
50%
Cooling load sent from Climatix to Carel.
Frequency inverter output
60%
Compr. no
Compressor number, 1 x compressor (C1)
Compr. Sum alarm
Alarm management
* * * * * * * *
Compressor_C1
Off/On
Compressor operating mode.
Suction gas temp_C1
17°C
Measured suction gas temp.
Evaporating temp_C1
10°C
Calculated evaporation temp based on low pres-
sure.
Overheating_C1
7 K
Measured overheating.
Expansion valve_1
65%
Expansion valve position.