Page 40
Operation and Maintenance
Envistar Top 04-21
DSET.190501.01.EN
Continuous product development may give rise to specification changes without notice.
9. Check the differential pressure across the rotor. The purging sector is
factory-installed, set to the maximum open position. Depending on the
unit’s pressure difference across the rotor, the purging sector may need
adjustment. An incorrect setting may impair the efficiency. Inspection and
adjustment should be carried out as follows:
- Measure and write down the differential pressure between the outdoor air
(P1) and the extract air (P3).
–
+
P2
P1
P4
P3
xx Pa
see table
below
Purging sector
- Read the recommended setting (adjustment hole in the purging sector) from
the table below.
Rotor vari-
ant
Adjustment hole in the purging sector
3
open*
2
intermediate
position
1
closed
Diff. pressure
between P1 and
P3 (Pa)
NO, NE
< 300
> 300
–
NP, NX
< 400
> 400
-
*
maximum open purge sector, preset position from the factory
- Adjust the purging sector if the need arises. The illustration shows the
purging sector set to the maximum open position.
Outdoor
air
Supply
air
Direction
of rotation
Extract
air
Exhaust
air
Schematic diagram - sizes and model may vary.