MOC safety
AL D06 Compressor Drive:
MOC_SAFETY
Motor Orientated Control has detected an error. The
inverter is stopped.
Errors must be remedied and alarms reset.
The alarm may be the result of a tripped high
pressure switch (the inverter loses all power). Reset
by pressing the button on the pressure switch.
Low DC voltage
AL D07 Compressor Drive:
DCLINK_VOLTAGE_LOW
The DC voltage in the inverter is too low.
The inverter is stopped.
When the voltage reaches the correct level the inverter
restarts.
Low pressure error
AL D09 Compressor Drive:
SUCTION_PRESS_INVALID
Faulty pressure signal for low pressure (suction side).
There is probably a fault with the wiring or sensor. The
inverter is stopped and restarts when the fault is fixed.
High pressure error
AL D10 Compressor Drive:
CONDENSEPRESS_INVALID
Faulty pressure signal for high pressure. There is
probably a fault with the wiring or sensor. The inverter is
stopped and restarts when the fault is fixed.
High pressure low
AL D12 Compressor Drive:
CONDENSER_PRESS_LOW
The pressure at the condenser is too low after starting.
After 10 repeated alarms, the error must be remedied
and the alarm reset.
Too many starts
AL D15 Compressor Drive:
RESTART_TOO_FREQUENTLY
The compressor has been restarted too many times in a
10-minute period and the inverter stopped.
The alarm needs to be reset.
Check that the air flow is correct.
Set the start delay for the compressor to 3 minutes after
the compressor is turned off.
For UC/MK/US: Check that the regulator that starts/
stops cooling mode is not too fast so that the cooling
mode hovers between ON and OFF. A maximum of
six starts are permitted in 10 minutes; an alarm will be
activated otherwise.
Internal inverter error
AL D16 Compressor Drive:
INTERNAL_ERROR
An internal communication error has been registered and
the inverter stopped. It is likely that the inverter cannot
be restarted if this error occurs.
Cooling unit alarm:
High pressure switch
AL C02 Compressor 1:
Alarm
Alarm from tripped high pressure switch.
Reset by pressing the button on the pressure switch.
Outdoor temp error
AL P01 B03 Ambient temp.
probe fault or disconnected
The inverter does not receive a value for the ambient
temperature and cannot regulate the compressor heat.
–
AL G01 Clock Board fault or
not connected
-
–
AL G02 Extended memory
Fault
–
Com.Modbus alarm
Danfoss: Alarm
AL D18 Modbus communica-
tion:
Compressor drive AOC
The alarm may be the result of a tripped high
pressure switch (the inverter loses all power).
Reset by pressing the button on the pressure switch.
AL D18 Modbus communica-
tion:
Compressor drive MOC
AL D18 Modbus communica-
tion:
Compressor drive EEV