Page 51
Operation and Maintenance
Envistar Top 04-21
DSET.190501.01.EN
Continuous product development may give rise to specification changes without notice.
6.9 Damper (code ETSP-UM, ETSP-TR, ETRL)
• ETSP-UM
Shut-off damper, rotary heat exchanger and counter-flow
exchanger
• ETSP-TR
Commissioning damper, rotary heat exchanger
• ETRL
Return air damper, rotary heat exchanger
The purpose of the dampers is to regulate the air flow. Faulty function gives rise
to disturbances that may result in serious problems.
•
If the outdoor air damper does not: - open completely this reduces the air
flow - close completely when the unit stops, the heating coil is likely to freeze
- seal properly (leaks) this will result in increased energy use.
•
If the trim damper for the rotor purging function is not working or is not cor-
rectly adjusted, possible odours in the extract air are likely to be transferred
via the rotor to the supply air.
Inspection
1. Check the function of the damper actuator.
2. Check the dampers for tightness when they are closed. If they are not
sealed, adjust the damper actuator to make the dampers tight (does not
apply to trim dampers).
3. Check the sealing strips.
4. If the damper is not working, check that there are no screws penetrating the
drive mechanism/damper blades to interfere with damper function.
Cleaning
Clean the damper blades with a cloth. In the event of stubborn dirt, use a mild,
alkaline detergent.
Damper size 04-21 (ETSP-UM, ETSP-TR, ETRL)
Damper TER-04 (ETSP-UM, ETSP-TR)