Page 56
Operation and Maintenance
Envistar Top 04-21
DSET.190501.01.EN
Continuous product development may give rise to specification changes without notice.
7.2 Cooling unit (code TEC) - size 06-12
Troubleshooting via symptoms
Symptom
Possible cause
Corrective action
The high pressure switch
has tripped
No or too low air flow across the
condenser
Check the air flow across the condenser.
The high pressure switch may have tripped
due to a momentary lack of air flow caused
by e.g. a closed damper, clogged filter or
incorrectly set time control program. Reset
the pressure switch manually.
Defective high pressure switch
Check/replace.
LOC alarm
Insufficient refrigerant volume
Look for leakage, seal the leak and top up
with refrigerant.
No or too low air flow across the
evaporator
Check/adjust the flow.
Defective expansion valve or low
pressure control
Check/replace.
The LED is off or flashing
green on the frequency
inverter (see also
information below)
Phase failure/voltage failure
Check the 1-phase supply, measure the
incoming voltage. Check the high pressure
switch by pressing the button. Reset
the frequency inverter by switching off
the voltage for 1 minute or more. Check
that the compressor is running without
dissonance.
Overload/defective stepless com-
pressor
Reset the frequency inverter by switching
off the voltage for 1 minute or more. Check
that the compressor is running without
dissonance.
Green light emitting diode (LED) on the inverter
There is a green LED on the inverter’s circuit board to indicate status:
Off –
No power supply or faulty power supply. If the LED is off in spite of correct power
supply, there could be an internal fault in the inverter.
Lit –
Normal mode, power supply is OK.
Flashing –
The inverter is indicating a problem. Read off the alarm according to "Alarm
information for inverter and compressor" page 57 and rectify.