Page 23
Operation and Maintenance Instructions
Envistar Top 04-21
DSET.181201.00.EN
Continuous product development may give rise to specification changes without notice.
5.5 Cooling Status – Cooling unit, size 06-12
With control equipment (code MX).
Status information can be read on the Climatix display (Main menu/Unit/Cool-
ing).
Value
Explanation
Danfoss-VSD
Danfoss Variable Speed Drive
High pressure
x.x bar Relative pressure from high pressure sensor.
Low pressure
x.x bar Relative pressure from low pressure sensor.
Compressor C1
On/Off Compressor operating mode.
Cooling unit status
Normal
Status of compressor.
Cooling unit alarm
OK/
Alarm
The alarm is displayed when the high pressure switch is tripped. In the
event of an alarm, see "High pressure switch alarm" page 56.
Alarm
No/Yes
The alarm is displayed if there is a fault with the inverter or compressor.
In the event of an alarm, see "Alarm IN for high pressure switch and
frequency inverter" page 26.
Safety mode
OK
VSD restr.
No
The inverter restricts the speed.
Cooling
x% Cooling load from Climatix cooling regulator.
Compr. frequency
x.xHz Frequency to the compressor.
Hot gas temp
x.x°C Hot gas temperature
****************************************
Danfoss-VSD-EEV
Electronic Expansion Valve
Suction gas temp
x.x°C Measured suction gas temp.
Evaporating temp
x.x°C Calculated evaporation temp based on low pressure.
Overheat. ref
x.xK Setpoint for overheating.
Adjusted automatically.
Overheating
x.xK Measured overheating.
Expansion valve
x.x% Expansion valve position.
****************************************
Danfoss-VSD-MOC
Motor Orientated Control
Inverter temp
x.x°C Internal temperature of the inverter.
Supply voltage
x.x V Supply voltage
C1 Output
x.x Wa Compressor output
Int. DC voltage
x.x V Internal DC voltage
Motor current phase
A
x.xx A
Power consumption phase A
Motor current phase
B
x.xx A
Power consumption phase B
Motor current phase
C
x.xx A
Power consumption phase C