Fan speeds are reduced from forced to normal if outdoors temperature drops below set limit (Outd.
Temp. fan). Fan speed returns to forced when outdoors temperature exceeds limit with more than 2°.
At climate adapted control fan speed sets linear from forced to normal out of set value (Outd. Temp.
fan forced and Outd. Temp. fan normal).
Settings
Setting
Description
Outd. Temp. fan
Normal:
-30 - +30
°
C
Fan speed limits to normal speed at outdoor temp. below
set value.
(Climate dep. vent., se chapter 2.8.4)
2.13 Outdoor compensated setpoint
IVC3 are configurable for outdoor temperature compensation of set point. Summer and/or winter
compensation are available. Two limits for outdoor temperature and a compensation value for each
summer and winter can be set.
Settings
Setting
Description
Outd comp summer
Temp 1
-30 - +30
°
C
Setpoint for start of summer compensation (at this point
there is no compensation)
Outd comp summer
Temp 2
-30 - +30
°
C
Setpoint for full summer compensation (at this point
compensation has is full influence on temp. control)
Outd comp summer
Comp
-30 - +30
°
C
The value that compensation would achieve at “Temp 2”
summer.
Outd comp winter
Temp 1
-30 - +30
°
C
Setpoint for full winter compensation (at this point
compensation has is full influence on temp. control)
Outd comp winter
Temp 2
-30 - +30
°
C
Setpoint for start of winter compensation (at this point there
is no compensation)
Outd comp winter
Comp
-30 - +30
°
C
The value that compensation would achieve at “Temp 1”
winter.
2.14 Extended operating time
Extended operating time initiates by an external switch via digital input (activated by a closing contact).
At extended operating time the unit runs with fans in forced speed
When external switch is turned off (open contact) the unit return to operate according to internal time
schedule.
Outdoortemp. (ºC)
Outdoor compensation
Outd. comp summer
Temp 1
Outd. comp summer
Temp 2
Outd. comp winter
Temp 1
Outd. comp winter
Temp 2
Outd. comp summer
comp.
Outd. comp winter
comp.
Setpoint displacement (ºC)