Fan speed is linear reduced from forced to normal when outdoor temperature decreases from “Outd.
Temp. fan forced” to “Outd. Temp. fan normal”.
Fans will gain forced speed immediately at cooling sequence even if climate controller hasn’t achieved
forced speed.
By input for external timer the fans will run on forced speed.
Settings
Setting
Description
Outd. Temp. fan
normal
-30 - +30
°
C
See fig. above
Outd. Temp. fan
forced
-30 - +30
°
C
See fig. above
2.9 Control sequence
Cooler, heat recovery (VVX) and heater will in sequence control the temperature. At warming demand
the output to cooler decreases, than VVX starts (with different run/stop intervals out of needs at digital
VVX or with an increasing output signal at analogue VVX) and finally increased output signal to
heater.
The sequence is opposite at cooling request.
Output SA, EA (V)
Outdoor (ºC)
Climate adapted control
Outd. Temp fan
normal
Outd. Temp. fan
forced
Normal
forced
Extract air control
Supply air control
Hysteresis 2º
0
10
Output signal (V)
HEATER
VVX
Recovery
COOLER
Set point
supply
Dead zon
2ºC
Supply temp. (ºC)
Sequences