background image

1.  Troubleshooting

Caution

   Before working on the pump, disconnect the power cord,

depressurize the discharge tubing and drain or flush any

residual liquid from the pump head and valves.

Problem

Possible Cause

Corrective Action

Faulty wiring

Correct wiring

Improper voltage

Connect to proper voltage source

Pump does not start

Electronic control unit is damaged

Replace control unit

Pump stroke length is too short

Operate pump with stroke length set at

100% until primed. Then set stroke

length as needed to obtain desired

output.

Air in suction tubing

Reroute suction tubing to eliminate air

trap

Valve gasket is missing

Install valve gasket

Valve set assembly direction is

wrong.

Reassemble valve set

Pump is air locked

Prime pump per instructions

Suction or discharge valve is

clogged with foreign matter

Disassemble, inspect, clean

Pump does not

prime

Ball stuck to valve seat

Disassemble, inspect, clean

Suction or discharge valve is

clogged with foreign matter

Disassemble, inspect, clean

Air is trapped in pump

Prime pump per instructions

Overfeeding

Install injection valve or back

 pressure valve

Diaphragm is damaged

Replace diaphragm

Output fluctuates

Worn check valves

Replace valve cartridges

Liquid leaks

Fitting or coupling nut is loose

Tighten

Pump head is loose

Tighten pump head bolts

Torque: 2.6 N.m

Diaphragm is damaged

Replace diaphragm

O-ring or valve gasket missing

Install o-ring or valve gasket

                                                       

       

- 36 -

Summary of Contents for EH-E

Page 1: ...IWAKI Electromagnetic Metering Pump Instruction Manual EH E Type Read this manual before use of product...

Page 2: ...Unpacking 6 2 Operation Principle 6 3 Specifications 7 4 Dimensions 10 2 INSTALLATION 14 1 Before Use 15 2 Location 16 3 Supply Tubing 16 4 Discharge Tubing 17 5 Electrical 17 3 OPERATION 18 1 Primin...

Page 3: ...or misapplication of the contents of the Warning section could lead to a serious accident including death or injury Caution Nonobservance or misapplication of the contents of the Caution section coul...

Page 4: ...n accordance with the pump specifications and application range Prohibited No remodeling Never remodel a pump Otherwise a serious accident may result Iwaki will not be responsible for any accident or...

Page 5: ...n If an electric part or wiring gets wet with the liquid spilled over accidentally a fire or electrical shock may be caused Install the system in a place free from liquid spillage or leakage Do not we...

Page 6: ...ndle the power cable carefully Electrical Shock Follow the instruction manual Replace the consumable part by following the descriptions in the instruction manual Do not disassemble any part of the pum...

Page 7: ...1 INTRODUCTION 1 Unpacking 6 2 Operation Principle 6 3 Specifications 7 4 Specifications of Control Unit 9 5 Dimensions 10 5...

Page 8: ...id When the solenoid coil is energized by the control unit the armature shaft moves forward due to the magnetic force of the solenoid The shaft is attached to a PTFE faced diaphragm which is part of t...

Page 9: ...onded to EPDM PTFE PVC Polyvinyl chloride Transparent GFRPP Glass fiber reinforced polypropylene M PVC Polyvinyl chloride Machined CE Alumina ceramics SUS316 316 Stainless steel FKM Fluoroelastomer EP...

Page 10: ...110V AC115V AC200V AC220V AC230V AC240V AC230V AC 90 126V AC 90 126V AC180 220V AC198 264V AC207 253V 50 60 Hz Lead wire P with plug No symbol without plug Controller E Special configuration 0 99 Poin...

Page 11: ...SH type install air chamber of approx 500 ml volume at the location as close to pump discharge port Adjustment Range Recommended stroke length adjustment range 20 to 100 Recommended frequency adjustme...

Page 12: ...5 Dimensions Material symbol VC V6 PC VM FC 10...

Page 13: ...5 Dimensions Material symbol VC V6 PC VM FC 11...

Page 14: ...5 Dimensions Material symbol SH 12...

Page 15: ...5 Dimensions Material symbol SH 13...

Page 16: ...2 INSTALLATION 1 Before Use 15 2 Location 16 3 Suction tubing 16 4 Discharge tubing 17 5 Electrical 17 14...

Page 17: ...start it from the beginning again Specified power only Do not operate the pump on voltage which is not specified on the name plate Failure to do so may result in damage or fire Only the specified powe...

Page 18: ...ks well See Figure 2 The supply tank or cover can also be used if it has provisions for mounting a pump See Figure 3 In any care the total suction lift should not exceed 1 5m 3 Supply tubing The suppl...

Page 19: ...tubing from sharp edges that could chafe or cut it If applicable install the injection valve at the injection point and connect the tubing to the injection valve 5 Electrical Connect the pump power c...

Page 20: ...Priming 19 2 Adjustment 20 3 Calibration 20 4 External Control 4 1 Display Keypad and Wiring Overview 21 4 2 Quick Reference 22 4 3 Digital Mode 23 4 4 Analog Mode STOP Function 24 4 5 AC Power Interr...

Page 21: ...kage may result Fasten the 4 hex socket bolts tightly before starting the initial pump operation The bolts may be loosened during storage or transportation of the pump depending upon the condition Fas...

Page 22: ...tputs are required it will be necessary to also reduce the stroke length Minimum recommended stroke length is 20 3 Calibration If exact output calibration is required first prime and adjust the pump a...

Page 23: ...ump is in standby mode EXT indicator Visible when pump is operating via external input STOP indicator Visible when the pump is stopped via external signal The pump stops pumping UP key Increases numer...

Page 24: ...rnal values Run manual decrease frequency 360 to 1 spm increase frequency 1 to 360 spm S S return to WAIT Run EXT S S return to WAIT SET external mode select DIG multiply or divide select ANA milliamp...

Page 25: ...start start start start start stop stop stop stop stop Run Run Set External Set External Manual External Mode Values Signal Operation Mode Signal Operation Mode Signal Operation Mode Signal Operation...

Page 26: ...ration 1 999 Divide operation 1 999 Multiply start operation X stop EXT EXT Set External Stand by Values mode WAIT Divide operation start Set value stop Signal Setting Mode Analog Input Operating Func...

Page 27: ...the value or will increase or decrease the m1ultiplier or divider Pressing a button once will change the value by one Holding a button down will continuously increment or decrement the value slowly at...

Page 28: ...from conductors and connect the positive side to terminal 5 and the negative side to terminal 8 2 Settings Start with pump in the WAITstate If it is not currently in wait press START STOP once 3 1 Se...

Page 29: ...eration of the pump A switch or solid state device capable of switching 5 VDC at 2 mA can be connected to terminals 6 positive and 8 negative of the terminal block Closing this circuit temporarily int...

Page 30: ...AC power is interrupted and then returned the functions return as shown below State before power is interrupted State after power returned WAIT WAIT Run manual Run manual Run external Run external Set...

Page 31: ...4 Maintenance 1 Maintenance 30 2 Diaphragm Replacement 30 3 Valve Replacement 30 4 Tubing 30 5 Names of Part and Structure 31 29...

Page 32: ...ad bolts to a torque of 2 6 N m 3 Valve Replacement Remove the suction and discharge tubing Remove the suction fitting two valve cartridges o ring and gasket s Install the new o ring gasket s and valv...

Page 33: ...5 Names of Part and Structure 1 Pump Head Unit Material symbol VC V6 PC P6 VM FC 31...

Page 34: ...5 Names of Part and Structure 2 Pump Head Unit Material symbol SH E30 E35 E45 32...

Page 35: ...5 Names of Part and Structure 3 Pump Head Unit Material symbol SH E55 33...

Page 36: ...t 12 Valve seat 13 Valve ball 13 Valve ball 14 Valve gasket 14 Valve gasket 18 Diaphragm spacer 17 O ring Gasket for type FC 19 Hex sock cap bolt 18 Diaphragm spacer 20 Plain washer 19 Hex sock cap bo...

Page 37: ...5 Troubleshooting 1 Troubleshooting 36 35...

Page 38: ...is missing Install valve gasket Valve set assembly direction is wrong Reassemble valve set Pump is air locked Prime pump per instructions Suction or discharge valve is clogged with foreign matter Dis...

Page 39: ...IWAKI CO LTD 6 6 Kanada sudacho 2 chome Chiyoda ku Tokyo 101 8558 Japan Tel 81 3 3254 2935 Fax 81 3 3252 8892 T308 1 99 2...

Reviews: