Figure 4: Wiring Diagram for Power Isolated applications
Connecting Input Devices
Chiller Water Supply Temperature (CWS)
To connect the chiller water supply thermistor to the unit, attach one wire from the thermistor to CWS (T19) and the
other wire to the adjacent common (T18). The thermistor used must be a 10K Precon Type III.
Chiller Water Return Temperature (CWR)
To connect the chiller water return thermistor to the unit, attach one wire from the thermistor to CWR (T17) and the
other wire to the adjacent common (T18). The thermistor used must be a 10K Precon Type III.
Condenser Supply Temperature (CDS)
To connect the condenser water supply thermistor to the unit, attach one wire from the thermistor to CDS (T16) and the
other wire to the adjacent common (T15). The thermistor used must be a 10K Precon Type III.
Condenser Return Temperature (CDR)
To connect the condenser water return thermistor to the unit, attach one wire from the thermistor to CDR (T14) and the
other wire to the adjacent common (T15). The thermistor used must be a 10K Precon Type III.