Copyright IXXAT Automation GmbH
CAN@net II - Manual, V1.4
Connections and indicators
10
3.1.3
CAN bus connector
The CAN@net II has a CAN bus interface according to ISO 11898-2. The signals
of the CAN bus interface are connected to the Sub D-9 plug (see table 3-1).
Pin No. Sub D9
Signal
1
Not connected
2
CAN low
3
GND
4
Not connected
5
Not connected
6
Not connected
7
CAN high
9
Not connected
9
Not connected
Table 3-3: Pin allocation of the CAN bus connector
The shield of the CAN connector is connected to the ground of the CAN bus in-
terface via a 1 M
Ω
resistor and a 1 nF capacitor.
For best noise immunity results, the shields of the CAN cables have to be
grounded.
3.2
Indicators
The CAN@net II has six LEDs. The LEDs show the communication status of the
relevant interface or the device status.
Picture 3-3: LEDs of the CAN@net II
Summary of Contents for CAN@net II