INSTALLATION REQUIREMENTS
!IMPORTANT!
TO ENSURE PROPER FUNCTIONALITY AND ADHERANCE TO BOTH LOCAL AND NATIONAL ELECTRIC
CODES, IT IS RECOMMENDED THAT SERVICE BE INSTALLED BY A LICENCED ELECTRICIAN EXPERIENCED
IN COMMERCIAL APPLICATIONS. INADEQUATE POWER AND WIRING MAY CAUSE THE UNIT TO PERFORM
ERRATICALLY, BLOW FUSES AND TIME INCORRECTLY.
GENERAL MECHANICAL:
•
ALL DIMENSIONS IN DRAWINGS ARE IN INCHES.
•
MOUNTING STUD SIZE 3/8” X 16 UNC X 1”.
•
4” MINIMUM CONCRETE REQUIRED AROUND MOUNTING STUD.
•
18” MINIMUM PAD RECOMMENDED FOR BUMPER CLEARANCE.
FOR GASOLINE DISPENSING LOCATIONS:
•
A
MINIMUM 18”
HIGH PAD ABOVE THE DRIVEWAY.
•
20 FOOT HORIZONTAL CLEARANCE
FROM THE EXTERIOR
ENCLOSURE OF ANY
GASOLINE DISPENSING PUMP.
ELECTRICAL SERVICE:
•
Dedicated service required
o
120V single phase
o
20 amp service
o
60Hz cycle
•
Minimum service wire size:
o
Less than 100ft run: 12Ga
o
100ft – 200ft run: 10Ga