- 32 -
A c t u a t o r s w i t h D P S P o s i t i o n e r
1.
switch off power supply and open the cover
2.
Put DIP-switches in neutral position (see fig. 1)
3.
put DIP-switch 1 to position „on “(see fig. 2)
4.
switch on the power supply
5.
put DIP-switch 1 back to neutral position
Electrical alignment
3
2
1
Manual alignment
The signals mode could be configurate by DIP-switches. Plug off the external power and positioner
plugs and easily configurated those switches as seen in the image below.
Configuration of signal
For change the working angel of the positioner system you have to adjust first the motor stop cam (position
“open” or “close”). Please note if you want to use the position confirmation of the voltfree contacts (plug 4) ,
you have to adjust the cams for it too, after you adjust the motor stop cams. For adjust the cams you can
get more information at our main manual,. After the adjustment of the cams you have to adjust the
positioner system too.
Adjust working angel
Note: At actuators with DPS and BSR you have to unplug the BSR Accupack from the circuit board before you
start the adjustment drive!
1.
switch off power supply and open the cover
2.
release plug 3 from terminal 3 (Positioning signal)
3.
make a bypass on terminal 3 between Pin 1 and Ground
4.
switch on the power supply
5.
release the bypass
6.
now the actuator drives in both end positions
Fig. 1
Fig. 2