JABLOTRON FUTURA
SYSTEM DESIGN GUIDE
Page 2/16
JABLOTRON LIVING TECHNOLOGY
1
1 .
. Technical specification
Technical specification
1
1 .. 1
1 .
. F u n ct ion a n d a p p lica t ion
F u n ct ion a n d a p p lica t ion
The Futura heat recovery unit represents HVAC equipment designed for controlled ventilation and treatment of the indoor environment. It
ensures heat and humidity recovery, filters supplied air, helps maintain optimum indoor humidity, and provides provides after-cooling by means
of an integrated fully automatic by-pass in summer, in the night mode. The unit is equipped with an enthalpy exchanger to utilize the latent
heat from humidity.
U n i t l o c a t i o n
U n i t l o c a t i o n
The heat recovery unit is installed vertically on the wall, in a room with a guaranteed minimal temperature of
+10 °C (+50 °F). Sufficient handling space shall be provided in front of the equipment for trouble-free access,
maintenance and servicing throughout the entire duration of its operation.
U n i t b o d y
U n i t b o d y
The internal structure of the heat recovery unit is made of monolithic EPP (expanded polypropylene) without
thermal bridges.
E n t h a l p y
E n t h a l p y
e x c h a n g e r
e x c h a n g e r
Enthalpy counter-current exchanger with humidity recovery control.
F i l t r a t i o n
F i l t r a t i o n
The heat recovery unit contains two filters: the F7 filter at the air supply as well as the exhaust. The
necessity to replace filters is indicated automatically and depends on the outside air quality of the location
where the device is used (approximately once every 2 - 6 months). The filtration can be supplemented with
an optional accessory in the form of a carbon filter, which is inserted directly into the unit under the supply
air filter.
C o n n e c t i n g d u c t
C o n n e c t i n g d u c t
The device is equipped with 4 EPP
∅
150 mm (5.9") flanges. EPP ducts are required at both the air inlet and
outlet to prevent the possibility of unwanted condensation occurring inside the inlet and outlet ducts.
D r y i n g a t
D r y i n g a t
e x t r e m e l y l o w
e x t r e m e l y l o w
o u t d o o r
o u t d o o r
t e m p e r a t u r e
t e m p e r a t u r e
Drying is activated when the outdoor temperature is lower than -20 °C (-4 °F) for more than 16 minutes.
Drying stops when the outdoor temperature is higher than -18 °C (-0.4 °F).
Low outdoor temperature
and
Caution
are displayed on the controller. After drying is finished, ventilation and filter control are blocked,
boost ventilation is limited to 2 minutes, and the unit continues to run in circulation mode.
E l e c t r i c a l
E l e c t r i c a l
c o n n e c t i o n
c o n n e c t i o n
Power socket 230V/50Hz with separate fuse 16A type B.
C o n t r o l
C o n t r o l
Integration in the MyJABLOTRON mobile application, which supports easy control of all the user functions and
settings, remote monitoring and administration and automatic alerting to filter replacement and error
conditions. Supplied with a wall-mounted control with an integrated CO
2
sensor (1 piece) as standard.
S u m m e r f u n c t i o n s
S u m m e r f u n c t i o n s
Fully automatic 100 % by-pass controlled according to the set preferred temperature.
O p t i o n a l
O p t i o n a l
e q u i p m e n t
e q u i p m e n t
CoolBreeze enthalpy heating/cooling module, forced exhaust (boost) buttons with operation indication; Rh,
SQA, CO
2